Station Statuses 1 To 3 - Siemens SIMATIC ET 200SP IM 155-6 DP HF Manual

Interface module
Hide thumbs Also See for SIMATIC ET 200SP IM 155-6 DP HF:
Table of Contents

Advertisement

5.3.2

Station statuses 1 to 3

Station statuses 1 to 3 provide an overview of the status of a DP slave.
Structure of station status 1 (byte 0)
Table 5- 7
Interface module IM 155-6 DP HF (6ES7155-6BA01-0CN0)
Manual, 10/2018, A5E03916550-AD
Structure of station status 1 (byte 0)
Bit
0
1: The DP slave is not responding to the DP
master.
1
1: The DP slave is not yet ready to ex-
change data.
2
1: The configuration data transferred from
the DP master to the DP slave does not
match the DP slave configuration.
3
1: External diagnostics is available. (Group
diagnostics display)
4
1: The required function is not supported by
the DP slave (for example, changing the
PROFIBUS address by means of software).
5
1: The DP master cannot interpret the re-
sponse of the DP slave.
6
1: The DP slave type does not match the
software configuration.
7
1: Parameters have been assigned to the
DP slave by a different DP master (not the
one that currently has access to the DP
slave).
Interrupts, error messages, diagnostics and system alarms
Meaning
Cause/Remedy
Is the correct PROFIBUS address set on
the DP slave?
Is the bus connector plugged in?
Is the DP slave connected to the voltage
supply?
Is the RS485 repeater properly config-
ured?
Wait; the DP slave is currently starting
up.
Has the correct station type or the cor-
rect DP slave configuration been en-
tered in the configuration software?
Evaluate the ID-specific diagnostics, the
module status, and/or the channel diag-
nostics. As soon as all errors have been
eliminated, bit 3 is reset. The bit is set
again when there is a new diagnostics
alarm in the bytes of the aforementioned
diagnostics.
Check the configuration.
Check the bus configuration.
Has the correct station type been en-
tered in the configuration software?
The bit is always 1, for example, if you
access the DP slave with the program-
ming device or another DP master.
The PROFIBUS address of the DP mas-
ter that assigned parameters to the DP
slave is located in the "Master
PROFIBUS address" diagnostics byte.
5.3 Alarms
41

Advertisement

Table of Contents
loading

Table of Contents