Description Of Parameters; Configuration Control - Siemens SIMATIC ET 200SP IM 155-6 DP HF Manual

Interface module
Hide thumbs Also See for SIMATIC ET 200SP IM 155-6 DP HF:
Table of Contents

Advertisement

Parameters/address space

4.2 Description of parameters

4.2
Description of parameters
4.2.1

Configuration control

You can use this parameter to enable the configuration control function in the ET 200SP
distributed I/O system.
Note
Configuration control
The "Configuration control" function can only be used if you set the parameter "Startup if
preset configuration does not match actual configuration" to yes at the same time.
Note
Configuring the enable
If you configure the enable, the ET 200SP distributed I/O system requires control data record
196 from the user program so that the ET 200SP distributed I/O system can operate the I/O
modules.
Reference
You can find additional information in the ET 200SP distributed I/O system
(http://support.automation.siemens.com/WW/view/en/58649293) system manual and in the
STEP 7 online help.
22
Interface module IM 155-6 DP HF (6ES7155-6BA01-0CN0)
Manual, 10/2018, A5E03916550-AD