Station Statuses 1 To 3 - Siemens SIMATIC IM151-1 STANDARD Manual

Et 200s distributed i/o interface module
Hide thumbs Also See for SIMATIC IM151-1 STANDARD:
Table of Contents

Advertisement

4.4.3

Station statuses 1 to 3

67B
Definition
Station statuses 1 to 3 provide an overview of the status of a DP slave.
Structure of station status 1 (byte 0)
Table 4- 3
Structure of station status 1 (byte 0)
Bit
0
1: The DP slave cannot be accessed by the DP
master.
1
1: The DP slave is not yet ready to exchange data.
2
1: The configuration data transferred from the DP
master to the DP slave does not match the slave
configuration.
3
1: External diagnostics information is pending.
(Group diagnostics display)
4
1: The required function is not supported by the DP
slave (for example, changing the PROFIBUS ad-
dress by means of software).
5
1: The DP master cannot interpret the response of
the DP slave.
6
1: The DP slave type does not match the software
configuration.
7
1: Parameters have been assigned to the DP slave
by a different DP master (not the one that currently
has access to the DP slave).
Interface module IM151-1 STANDARD (6ES7151-1AA06-0AB0)
Manual, 07/2015, A5E01075950-AD
Meaning
Interrupt, error, and system messages
Cause/Remedy
Is the correct PROFIBUS address set on the DP slave?
Is the bus connector plugged in?
Is the DP slave connected to the voltage supply?
Is the RS-485 repeater set correctly?
Has the DP slave been reset?
Wait, the DP slave is currently starting up.
Has the correct station type or the correct DP slave con-
figuration been entered in the configuration software?
Evaluate the ID-specific diagnostics information, the mod-
ule status, and/or the channel-specific diagnostics infor-
mation. As soon as all errors have been eliminated, bit 3
will be reset. The bit will be set again when there is a new
diagnostics message in the bytes of the aforementioned
diagnostics.
Check the configuration.
Check the bus configuration.
Has the correct station type been entered in the configura-
tion software?
The bit is always 1, for example, if you access the DP
slave with the programming device or another DP master.
The PROFIBUS address of the DP master that assigned
parameters to the DP slave is located in the "Master
PROFIBUS address" diagnostics byte.
4.4 Diagnostics with STEP 7
43