Siemens SIMATIC ET 200SP IM 155-6 DP HF Manual page 36

Interface module
Hide thumbs Also See for SIMATIC ET 200SP IM 155-6 DP HF:
Table of Contents

Advertisement

The following table is used to explain the channel error entries:
Channel number
Channel properties
Channel error type
Interface module IM 155-6 DP HF (6ES7155-6BA01-0CN0)
Manual, 10/2018, A5E03916550-AD
Interrupts, error messages, diagnostics and system alarms
Description
0 to 63: Channel number for channel error
0x8000: Entire submodule
Bit 0 to 7
00
: Free data type
H
01
: bit
H
02
: 2 bit
H
03
: 4 bit
H
04
: byte
H
05
: word
H
06
: Double word
H
07
bis FF
H
H
Bit 8
0: Channel
1: Channel group
Bit 9, 10
00
: Diagnostics
H
01
: Maintenance demanded
H
02
: Maintenance required
H
03
: Reserve
H
Bit 11, 12
00
: Channel error-free
H
01
: Incoming diagnostics
H
02
: Outgoing diagnostics
H
03
: Outgoing diagnostics, but other diagnostics are also
H
pending on this channel
Bit 13 to 15
00
: Reserve
H
01
: Input channel
H
02
: Output channel
H
03
: Input/output channel
H
Refer to respective manual for explanation.