Programming Of Functioncodes - Hengstler tico 732 User Manual

Bidirectional multifunction-counter
Table of Contents

Advertisement

2.2
Programming of function codes
Programming mode:
press while
switching
Power on
function
basic settings
count mode
decimal point
(on display)
reset/setmode
signal time
output 1
signal time
output 2
Output with
reset
pnp/npn-
selection
input
attentuation
dyn./static
Reset
output
signal memory
additional
totalizer
keylock for
reset key 6+4
keylock
for preset 1
keylock
for preset 2
keylock
for prescaler
keylock mode
(F20-F23)
* default values
1
bidirectional counting with single evaluation (eg. for encoders with 2 channels A,B)
2
parameter only appears for preset version
3
with appliances with one preset only, this applies to preset 1 and output 1 (OUT 1)
4
Input B passive (0V at PNP or 24V at NPN or open)
Input B active (24V at PNP or 0V at NPN)
Sach-Nr. 2 732 017; Version 1310301WBI
Change parameter:
press
code
alternatives/signification
F0
0*
no function
1
all function codes are set to the default values (*-marked)
F1
Input A
0 *
count Input
1
count Input
2
count Input
3
adding
4
adding
5
adding
6
channel A
7
channel A
F3
0*
no decimal point
1
one decimal place (xxxxx.x)
2
two decimal places (xxxx.xx)
3
three decimal places (xxx.xxx)
F4
0*
reset to „0", no autoreset
1
reset to „0", with autoreset when reaching preset 2
2
set to preset 2, no autoreset
3
set to preset 2, with autoreset when reaching „0"
2
F6
OFF
no Output signal
On
bistable Output signal (latching), will be deleted by Out 2
0,02
20 ms
0,05
50 ms
0,10*
100 ms
0,20
200 ms
0,50
500 ms
1,00
1 s
F7
2
see
see above; signal time output 1
above
F9
0*
Do not activate the main preset output (OUT 2)
1
Activate the main preset (OUT 2)
F10
0
npn with 8V level (negative)
1*
pnp with 8V level (positive)
2
npn with TTL-level
3
pnp with TTL-level
F11
0
30 Hz attenuation (for contacts)
1 *
no attentuation, 5 kHz (bidirectional counting: 2,5 kHz)
F12
0*
static reset
1
dynamic reset (counting possible during reseting)
F14
0*
after power fail, the signal times will not be restarted
1
after power fail, the signal times will be restarted
F15
0*
disabled
1
enabled
F20
0*
key reset is possible
1
key reset is not possible (or possible with delay see F29)
2
F21
0*
access to preset 1 is possible
1
access to preset 1 is not possible (or delayed see F29)
2
F22
0*
access to preset 2 is possible
1
access to preset 2 is not possible (or delayed see F29)
F23
0*
access to prescaler is possible
1
access to prescaler is not possible (or delayed see F29)
F29
0*
access to parameters from F20-F23 is possible after
holding the keys for more than 10 sec.
1
access to parameter is not possible
Count direction negative
Change to the next function:
press
Input B
Input C
gate
reset
4
direction(u/d)
reset
direction(u/d)
4
gate
subtracting
reset
subtracting
gate
adding
reset
1
1
channel B
reset
1
channel B
1
gate
2+3
3
in case of reset
Count direction positive
Return to count mode:
press > 5 s e c
2+3
2+3
3
in case of Reset
7/28