Auto-tuning Error

When a fault occurs during auto-tuning of a standard AC motor, the display will show the "AtErr" fault and the
motor stops. The fault information is displayed in parameter 17-11.
Note: The fault contact output does not energize with an auto-tuning fault. Refer to Table 10.4.1, for fault infor-
mation during tuning, cause and corrective action.
Error
01
Motor data input error.
02
Motor lead to lead resistance R1 tuning
error.
03
Motor leakage inductance tuning error.
04
Motor rotor resistance R2 tuning error.
05
Motor mutual inductance Lm tuning error.
07
Deadtime compensation detection error
06
Motor encoder error
08
Motor acceleration error (Rotational type
auto-tuning only).
09
Other
5.5.

PM Motor Auto-tuning Error

When a fault occurs during auto-tuning of a PM motor, the display will show the "IPErr" fault and the motor
stops. The fault information is displayed in parameter 22-18.
Note: The fault contact output does not energize with an auto-tuning fault. Refer to Table 10.5.1, for fault infor-
mation during tuning, cause and corrective action.
Error
01
Magnetic pole alignment tuning failure
(static).
02
PG option missing.
03
Magnetic pole alignment auto-tuning abort
during rotational auto-tune.
04
Timeout during magnetic pole alignment
during rotational auto-tune.
05
Circuit tuning time out.
06
Encoder error
07
Other motor tuning errors.
08
Motor current out of range during magnet-
ic pole alignment (rotational auto-tune).
09
Current out of range during circuit tuning.
10
Magnetic pole alignment and circuit tuning
failed.
VDI100 • Start-up and Installation Manual
Table 10.4.1 Auto-tuning fault and corrective actions
Description
• Motor Input data error during auto-tu-
ning.
• Inverter output current does not match
motor rated current.
• Auto-tuning is not completed within the
specified time
• Auto-tuning results fall outside parame-
ter setting range.
• Motor rated current exceeded.
• Motor was disconnected.
• PG feedback noise
• Motor fails to accelerate in the specified
time (00-14= 20sec).
• No load current is higher than 70% of the
motor rated current.
• Torque reference exceeds 100%.
• Errors other than ATE01~ATE08.
Table 10.5.1 Auto-tuning fault and corrective actions for PM motor
Description
• Inverter output current does not match
motor current.
• Magnetic pole cannot be aligned without
PG option card.
• System abnormality during magnetic
pole alignment.
• Motor cannot rotate
• System abnormality during circuit
tuning.
• PG feedback noise
• Other tuning errors.
• Motor cannot operate at low speeds.
• Inverter output current does not match
motor current.
• Auto-tuning is not successful.
Cause
• Check the motor tuning data (17-00 to
17-09).
• Check inverter size
• Check the motor tuning data (17-00 to
17-09).
• Check motor connection.
• Disconnect motor load.
• Check inverter current detection circuit
and DCCTs.
• Check motor installation
• Check motor rated current.
• Check PG card grounding.
• Increase acceleration time (00-14).
• Disconnect motor load
• Check the motor tuning data (17-00 to
17-09).
• Check motor connection.
Cause
• Check the motor tuning data (22-02).
• Check inverter size
• Install PG feedback card.
• Check for active protection functions
preventing auto-tuning.
• Check motor.
• Check motor wiring.
• Check brake released.
• Check for active protection functions
preventing auto-tuning.
• Check motor rated current.
• Check PG card grounding.
• Check the motor tuning data (22-02).
• Check motor connection
• Check PG card wiring
• Check motor connection.
• Check the motor tuning data (22-02).
• Check inverter size
• Retry magnetic pole alignment and
circuit tuning.
Corrective action