Select the connection type: Ethernet.
IP: IP address acquired by the inverter
Port: 502
Modbus node: 01
Alias: ISS 1Play
Phase: R
SOC maximum: This value is informative. Not used for the monitoring strategy.
Set the same value as the INGECON SUN STORAGE 1Play as SOC MAX.
SOC minimum: Not used for the monitoring strategy. Set the same value as the
INGECON SUN STORAGE 1Play as SOC MIN.
Click on Find . If the unit is correctly connected and configured a warning is
displayed with the device's serial number and firmware.
Finally, save the settings by clicking on Save .
5. Configure the GRID reading.
Click on the Grid icon and configure the Power Meter Id parameter with the name
provided to the previously configured ISS 1Play .
ABH2013IQM05_A.docx
Installation and configuration of a self consumption system managed by
INGECON SUN STORAGE 1Play