Parámetro
TEMP. COMP.
To activate the compensation temperature, enter via the Display:
Menu > Configuration > Battery > Battery Type > Lead-Acid > PT100 Battery Sensor
Once configured, save the changes.
2. AC installation type
Identify correctly the TT or TN grounding system of the installation before
proceeding with the configuration.
This section is for selecting the type of grid and its parameters. Enter via the Display:
Menu > Configuration > Grid/Genset > Type of Grid > Grid > Country regulations
Select the corresponding country regulations and confirm by clicking on "OK". Save the
changes.
Next, configure the neutral system TT or TN of the public grid. Enter via the Display:
Finally, configure the parameters of the AC grid. Enter via the Display:
Enter the following parameters:
Setting
RMS VOLTAGE
FREQUENCY
AC PHASE
Once configured, save the changes.
3. Operation Mode
For operation in the self consumption installations managed by INGECON SUN STORAGE 1Play,
it is necessary to configure the inverter operation mode in the "Self consumption" mode.
For more information about the operation of this type of installation, see the
"Technical guide for installations with INGECON SUN STORAGE 1Play"
available on the Ingeteam website.
Enter via the Display:
Menu > Configuration > Operation Mode > Mode > Self consumption
Enter the following parameters:
ABH2013IQM05_A.docx
Installation and configuration of a self consumption system managed by
INGECON SUN STORAGE 1Play
Compensation temperature of a cell (-mV/ºC/Cell), specified by the battery
manufacturer. The default value is -4mV/ºC/Cell.
Menú > Configuration > Grid/Genset > TT/TN System
Menu > Configuration > Inverter
Rated voltage of the AC grid (V).
Rated frequency of the AC grid (Hz).
Single-phase system of the AC grid. Configure with the 0 value "Single
Phase".