Henny Penny Velocity Series Service Manual page 16

Pressure fryer
Hide thumbs Also See for Velocity Series:
Table of Contents

Advertisement

Menu
Item
(Mod-
e)
T-36
T-37
T-38
T-39
T-40
T-99
6
Display
ANY FILL: LVL PROBE
MIN DETECT
CHANGE TECH CODE
TOTAL INIT
HEAT PULSE ENABLED Always displays YES, and is not changeable.
PROTECTION PROBE
Mix/ATO/Polish
Function
that indicates the oil has refilled high enough to reach
or splash on that probe.
How the control monitors the level probe for a tempera-
ture rise when refilling the pot is described in the de-
tails of step T-34. This T-36 parameter specifies a
minimum reasonable filling time for that temperature
rise to be trusted.
The default Tech Mode password can be changed by
the user. This password is used for entry to Tech Mode
and Stats Mode. It is recommended that this password
not be changed except under extreme circumstances,
as a service technician visiting the store to service the
fryer would probably not know the new password and
would not be able to access Tech Mode.
Press and hold the button next to hold on the display to
initialize the control board.
Manually turn on the protection probe feature. Must up-
grade software to v1.60 to use this feature. For soft-
ware v1.60 and after, the control auto-detects whether
the probe is connected when the fryer enters the melt
cycle for the first time and sees the probe 50°F hotter
than the main temp probe.
Appears in Tech Mode is activated during Startup
Mode. Lets a technician cancel Start-up mode – just for
the pending start-up.