Table of Contents

Advertisement

SmartLi
User Manual
Alarm
Alarm Name
ID
0021
Battery EOD
0023
Battery
overtemperature
0024
Battery
undertemperature
0025
Battery
overvoltage
0026
Battery
undervoltage
0027
Battery
overcurrent
Issue 04 (2019-09-16)
Severity
Cause
Critical
The battery voltage reaches
the EOD threshold due to
continuous discharge.
Minor
The cell temperature is too
high.
Minor
The cell temperature is too
low.
Minor
The battery voltage
reaches the high-voltage
alarm threshold.
The cell temperature is too
high.
Minor
The battery voltage
reaches the low-voltage
alarm threshold.
The cell temperature is too
low.
The input fuse is blown.
Minor
The battery charge current
reaches the overcurrent
alarm threshold.
The battery discharge
current reaches the
overcurrent alarm
threshold.
Copyright © Huawei Technologies Co., Ltd.
A
Alarm List
Solution
Check the status of the
battery cabinet and turn on
the BCB switch.
Check the mains, and
charge batteries in a timely
manner.
Take measures to reduce the
ambient temperature.
Take measures to increase the
ambient temperature.
Check the UPS status.
Check the lithium battery
cabinet status.
Check whether the input
fuse is normal.
Check the mains, and
charge batteries in a timely
manner.
Restore the mains input to
the UPS and start the
charger to charge the
battery.
Check the UPS charger
status.
Check the lithium battery
cabinet status.
Check whether the UPS is
overloaded. Reduce the UPS

A Alarm List