3.1 Installation Preparations

3.1.1 Site

3.1.1.1 Installation Environment

3.1.1.2 Installation Clearances

Reserve the following clearances around the cabinet to facilitate operations and ventilation:
Issue 04 (2019-09-16)
Do not install the SmartLi in high temperature, low temperature, or damp environments.
Install the SmartLi away from water sources, heat sources, and flammable or explosive
materials.
Keep the SmartLi away from direct sunlight, dust, volatile gases, corrosive materials,
and air dense with salt particles.
Do not install the SmartLi in environments with conductive metal scraps in the air.
Do not install the SmartLi in the FusionModule smart module. You need to install it in an
independent battery room and keep it far away from the IT and network equipment.
Reserve at least 800 mm from the front of the cabinet.
Reserve at least 500 mm from the top of the cabinet.
The SmartLi can be installed against a wall and no space needs to be reserved at the rear.
If an antiseismic kit is deployed, at least 500 mm space should be reserved at the rear for
operations.