Digital Outputs − P181 And P182 - Lennox NTC1-1-Kit Installation Instructions Manual

Network thermostat controller
Table of Contents

Advertisement

H1=Heating Stage 1
H2=Heating Stage 2
Figure 10. Discharge Air Control Heating (DACH) Stages − Default Values Shown
Digital Outputs − P181 and P182
Each output is a fused, dry contact and is rated for 24VAC,
two amp maximum.
Refer to the appropriate unit in tables 6 through 9 to
determine the digital output resulting at different thermostat
inputs. The appropriate digital output LED will be energized
at the same time. The output can also be read with a
voltmeter at P181 and P182. Configuration DIP switches
should be set as shown in tables 3 through 5 for each
type of unit. When an air handling unit is installed, the " G"
output is energized during the occupied time period. See
system parameter A4.01.
All output tables show the G blower output during the
unoccupied time period. During the occupied time period
blower operation will be continuous. If A4.01 system
parameter is changed to option 0, the blower will operate
as shown in tables regardless of time period.
Output tables do not show blower on/off delays.
Table 6. Electric Cool / Gas Heat Units
Thermostat
P181
Demand
Y1
Y2
1st Cool
ON
OFF
OFF
2nd Cool
ON
ON
OFF
3rd Cool
ON
ON
Low Heat
OFF
OFF
OFF
High Heat
OFF
OFF
OFF
115
114
113
112
111
110°F
Default Occupied
110
DACH Setpoint
109
ECTO A4.08
108
107
106
105
104
NTC Digital Output
P182
Y3
W1
W2
0
B
OFF
OFF
N/A
N/A
OFF
OFF
N/A
N/A
ON
OFF
OFF
N/A
N/A
ON
OFF
N/A
N/A
ON
ON
N/A
N/A
110°F + 5°F
ECTO A4.08 + A4.09
OFF
H1
ON
A4.10
DACH S tage−Up Delay 3 minutes
A4.11
DACH S tage−Down Delay 2 minutes
Compressor Minimum Run Times Apply
Table 7. Electric Cool / Electric Heat Units
Thermostat
Demand
1st Cool
2nd Cool
3rd Cool
Low Heat
High Heat
Thermostat
Demand
1st Cool
2nd Cool
3rd Cool
Low Heat
High Heat
G
ON
ON
ON
OFF
OFF
Page 7
5°F
DACH Deadband
(All Stages Same Setting)
°
°
°
110
F − 2
F + 5
F
ECTO A4.09 − A4.12 + A4.09
OFF
H2
ON
°
°
110
F − 2
F Di
ECTO A4.08 − A4.12
NTC Digital Output
P181
Y1
Y2
Y3
W1
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
Table 8. Heat Pump Units Type 1
NTC Digital Output
P181
Y1
Y2
Y3
W1
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
P182
W2
0
B
G
OFF
N/A
N/A
ON
OFF
N/A
N/A
ON
OFF
N/A
N/A
ON
OFF
N/A
N/A
ON
ON
N/A
N/A
ON
P182
W2
0
B
G
OFF
N/A
N/A
ON
OFF
N/A
N/A
ON
OFF
N/A
N/A
ON
OFF
N/A
N/A
OFF
ON
N/A
N/A
OFF