Inputs/Outputs Section (Table 7) - Lennox DELTA 2 System Programming Manual

Microprocessor controller
Table of Contents

Advertisement

Screen Ref –13
T
EXT
Sensor Offset – Return Air Temp
Sensor Offset – Humidity
Screen Ref –14
T
EXT
Sensor Offset – Supply Air Temp
Sensor Offset – Enter Water Temp
Screen Ref – 15
T
EXT
Sensor Offset – External Air Temp
Sensor Offset – Leaving Water
Screen Ref –16
T
EXT
Man Procedure – Fan (Master)
Man Procedure – Fan (Slave)
Screen Ref –17
T
EXT
Man Procedure – Heater 1
Man Procedure – Heater 2
Screen Ref –18
T
EXT
Man Procedure – Alarm NS
Man Procedure – Alarm S
Screen Ref –19
T
EXT
Man Procedure – Compressor 1
Man Procedure – Compressor 2
Screen Ref –20
T
EXT
Man Procedure – AOUT 1
Man Procedure – AOUT 2
Screen Ref –21
T
EXT
Man Procedure – AOUT 3
Man Procedure – AOUT 4
Screen Ref –22
T
EXT
Humidifier
Auto Drain Enable
Drain Interval
Drain Length
Screen Ref –23
T
EXT
Disable Humidifier
Manual Drain
Notes :
1. With unit on/off set as off, screens 16 – 21 are available for manual enable of all analogue & digital outputs.
D
2
ELTA
Microprocessor Controller.
Table No. 6
O
F
PTION
ACTORY
+/-9.9 C
00.0 C
+/-9.9 %
0.0%
O
F
PTION
ACTORY
+/-9.9 C
00.0 C
+/-9.9 C
00.0 C
O
F
PTION
ACTORY
+/-9.9 C
00.0 C
+/-9.9 C
00.0 C
O
F
PTION
ACTORY
Y/N
N
Y/N
N
O
F
PTION
ACTORY
Y/N
N
Y/N
N
O
F
PTION
ACTORY
Y/N
N
Y/N
N
O
F
PTION
ACTORY
Y/N
N
Y/N
N
O
F
PTION
ACTORY
0.00V
0.00V
0.00V
0.00V
O
F
PTION
ACTORY
0.00V
0.00V
0.00V
0.00V
O
F
PTION
ACTORY
Y/N
N
00Hr
05Hr
000Sec
120Sec
O
F
PTION
ACTORY
Y/N
N
Y/N
N
System Programming Manual.
CONTINUED
S
D
ET
ESCRIPTION
Allows Sensor Recalibration. +/- 9.9 C Available
Allows Sensor Recalibration. +/- 9.9 % Available
S
D
ET
ESCRIPTION
Allows Sensor Recalibration. +/- 9.9 C Available
Allows Sensor Recalibration. +/- 9.9 C Available
S
D
ET
ESCRIPTION
Allows Sensor Recalibration. +/- 9.9 C Available
Allows Sensor Recalibration. +/- 9.9 C Available
S
D
ET
ESCRIPTION
Allows Manual Running of Fan ( Master Fan)
Allows Manual Running of Fan ( Slave Fan )
S
D
ET
ESCRIPTION
Allows Manual Running of Heater 1
Allows Manual Running of Heater 2
S
D
ET
ESCRIPTION
Allows proving of Non Serious Alarm Output
Allows proving of Serious Alarm Output
S
D
ET
ESCRIPTION
Allows Manual Running of Compressor 1
Allows Manual Running of Compressor 2
S
D
ET
ESCRIPTION
Allows Manual Setting of Analogue Output 1
Allows Manual Setting of Analogue Output 2
S
D
ET
ESCRIPTION
Allows Manual Setting of Analogue Output 3
Allows Manual Setting of Analogue Output 4
S
D
ET
ESCRIPTION
To enable automatic humidifier drain
From 00 to 10Hr
From 000 to 240Sec
S
D
ET
ESCRIPTION
Allows Disabling of Humidifier
Allows Manual Humidifier Drain of 120 Seconds
12