Wiring; 24Vac; Communication Wiring; Typical Ntc1−1 (A113) Field Wiring - Lennox NTC1-1-Kit Installation Instructions Manual

Network thermostat controller
Table of Contents

Advertisement

Wiring

All wiring must comply with local electrical code or as
specified on the unit wiring diagrams. Refer to figure 1
for field wiring connections. Example wiring diagrams are
provided in the back of this manual.

24VaC

Connect 24VAC power to P176−1 and 2 from a class 2
transformer using standard 18AWG thermostat wiring.
P176−2 (common) must be connected to earth ground.
t
NtC1−1 (a113) f
ypiCal
All inputs connected to P178
and P179 are optional. See
System Mode sections for
P178 options.
COM
*
Connect air ow switch
and N.C. terminals to
24VAC and common if not
used. Service switch and
N.O. switch are optional.
P176
P177
P178
P179
P181
P182
Pushbutton
Short push: By−passes on/o delays
Long push: Resets NTC
ADDRESS DIP Switch
Address DIP is used for setting the unit address
when connected to the L Connection network.
Switches add for a total of 31 addresses (1 to 31).
NTC must be reset after changing an address.
w
ield
iriNg
INPUTS
1
+
CO
CO
(0−10VDC)
2
2
+
RH
RH (0−10VDC)
+
DMP
DAMPER FB (2−10VDC)
P179
1
1
ZONE
2
O
(A2)
3
RETURN
4
(RT16)
5
DISCHARGE
O
6
(RT6)
7
OUTDOOR
8
(RT17)
P178
HB
24VAC
1
*
+
AIR FLOW
SWITCH
+
SERVICE
*
+
N.C.
+
N.O.
_
P177
Power in − 24VAC
Digital inputs − 24VAC or DC
T emperature sensors − thermistor type
Analog inputs − CO2, RH − 0 1− 10VDC,
Damper FB 2−10VDC
Relay outputs − 24V (AC or DC) 2A max
Relay outputs − 24V (AC or DC) 2A max
EXAMPLE
OF UNIT
ADDRESS 13
4 8 16
2
1
1 + 4 + 8 = 13
Figure 13. Typical NTC1−1 (A113) Field Wiring
C
ommUniCaTion
Cable type: Lennox P/N 94L63 or 27M19, Belden type
88761 or equivalent. (22AWG stranded or twisted pair,
100% aluminum shield with drain wire, Teflon jacket).
Daisy chain the communications cable between each NTC
and NCP as shown in "Figure 11. L Connection Network
Daisy−chain Communication Wiring" on page 9". Do
not connect the shield drain wire to the NTC " G".
NOTE: Make sure the total run of communications wiring
does not exceed 4000 feet (1219 m).
OFF AUTO ON
UNIT
ADDRESS
1 2 4 8 16
N
SW1
CONFIG
12 3456 78
N
2A FUSE
P181 and P182 outputs are iso-
lated and may be connected to dif-
ferent transformers. Each output
has a 2 amp fuse.
HP REVERSING VALVE
XMIT
24VAC power input
POWER IN
has a 2 amp fuse.
HOT
1
L Connection
24VAC
communica-
10VA
tion bus
MIN.
LED's
Heartbeat LED:
Green 1 sec. on/o = Normal operation
Green 3 sec. on/o = Delay initiated
Red 1 sec. on/o = No run lock−out
XMIT Transmit LED:
Yellow − = Data is being transmitted
Blink rate varies − as slow as once every 30
seconds when many units are on the network
Digital Input LED's:
AFS−Yellow steady= Blower is operating
Service−Yellow steady= Indicates the service
input is energized.
N.C.−Yellow steady= Indicates the N.C. input
is energized.
N.O.−Yellow steady=Indicates the N.O. input
is energized.
Thermostat Output LED's:
Green, red, or yellow steady=Indicates relay is
closed.
Page 13
w
iRing
OUTPUTS
P181
Y1
NO
Y1
R
C
Y2
NO
Y2
C
Y3
NO
Y3
C
W1
NO
W1
C
1
P182
W2
W2
NO
C
G
G
NO
C
OCP
NO
OCP
C
C
O
O
B
B
1
Con guration DIP SW10
TYPE
1
2
Electric HEAT OFF OFF
HP Type 1
ON
OFF
HP Type 2
OFF ON
Gas Heat
ON
ON
COMMON
COOL
3
4
P176
1−Stage cool
OFF OFF
2−Stage cool
ON
3−Stage cool
ON
HEAT
5
6
GND
No heating
OFF OFF
1−Stage heat
ON
2−Stage heat
OFF ON
Temperature Thermistor
Resistance
RT6, RT16
RT17
A2
30°F
34,566
NA
40°F
26,106
NA
50°F
19,904
0,904
60°F
15,313
6,313
70°F
1 1,884
2,884
80°F
9,298
0,298
90°F
7,332
8,332
100°F
5,826
NA
All values are +/− 2%.
OFF
ON
OFF
2
1
1
1