Heatpump Controller; (Pl-C1000-Hp & Pl-C1000-Hps) - Prolon C1000 Series Quick Start Manual

Hide thumbs Also See for C1000 Series:
Table of Contents

Advertisement

Heatpump Controller

32-122 °F (0-50 °C) Non-condensing
10
REV 2.0 / PL-QCK-C1000-EN
(PL-C1000-HP & PL-C1000-HPS)
PL-C1000-HP
PL-C1000-HP
INT Port: Incoming RS485
INT Port: Incoming RS485
network communication
network communication
(Modbus)
(Modbus)
NET Port: Outgoing RS485
NET Port: Outgoing RS485
network communication
network communication
to zones (Modbus)
to zones (Modbus)
External dry contact for night setback or proof of fan
External dry contact for night setback or proof of fan
Supply temperature sensor (10K thermistor)
Supply temperature sensor (10K thermistor)
Common for all the inputs
Common for all the inputs
Return temperature sensor (10K thermistor)
Return temperature sensor (10K thermistor)
Outside temp (10K therm), water intake temp (10K therm)
Outside temp (10K therm), water intake temp (10K therm)
or dry contact for alarm
or dry contact for alarm
Output 5 - Preheating /
Output 5 - Preheating /
Aux Heat / Econo
Aux Heat / Econo
Output 4 - Aux Heat
Output 4 - Aux Heat
Output 3 - Rev Valve
Output 3 - Rev Valve
Output 2 - Compressor 1
Output 2 - Compressor 1
Output 1 - Fan (G)
Output 1 - Fan (G)
Controller's power source
Controller's power source
Unit's R&C terminal (24VAC)
Unit's R&C terminal (24VAC)
1 Compressor
1 Compressor
cULus Listed; UL 916 Energy Management Equipment, File E364757, Vol.1
REV 2.0 / PL-QCK-C1000-EN
PL-C1000-HPS
PL-C1000-HPS
INT Port: ProLon digital temperature
INT Port: ProLon digital temperature
sensor - OR - Incoming RS485
sensor - OR - Incoming RS485
network communication (Modbus)
network communication (Modbus)
NET Port: ProLon digital temperature
NET Port: ProLon digital temperature
Sensor - OR - Incoming RS485
Sensor - OR - Incoming RS485
network communication (Modbus)
network communication (Modbus)
Output 5 - Aux Heat
Output 5 - Aux Heat
Output 4 - Rev Valve
Output 4 - Rev Valve
Output 3 - Compressor 2
Output 3 - Compressor 2
Output 2 - Compressor 1
Output 2 - Compressor 1
Output 1 - Fan (G)
Output 1 - Fan (G)
Controller's power source
Controller's power source
Unit's R&C terminal (24VAC)
Unit's R&C terminal (24VAC)
2 Compressors
2 Compressors
11