E528 RF Installation
Typically only a wired door switch contact would be
required for this application (can also use wireless door
switch contact) or possibly a remote temperature sensor. In
this case, using the harness (P/N 62-1467), refer to low-
voltage communications connections table.
Connect harness (P/N 62-1467) to H5 of e528.

Power and Actuator Connections

Refer to line voltage connections table
Use wire nuts to connect the 10-pin Molex wiring harness to
the power and valve/fan control signal wires within the
electrical box. See pre defined commissioning document
which describes the specific wire connections for the
application
Plug the pre-wired 10-pin connector into the female
receptacle at the back of the e528. Note: this will connect the
unit to the input power and relays to the loads.
d
c
Figure 7 E528.4G Connections
Note: When using mixed voltage, voltage separation must be
maintained. Line voltage must reside in the right side of the gang
box. Low voltage must reside in the left side of the gang box.
Hook the tabs at the top rear of the e528 housing into the
matching depressions at the top of the mounting plate and
rotate the bottom of the housing toward the wall until it
snaps into place on the mounting plate.
Secure the housing to the mounting plate with the two small
screws removed in Step 1 of the Mounting section.
Apply power to the e528 by closing the applicable supply
breaker. Verify that the e528 powers up. Values should
begin appearing on the LCD display.

Commissioning

The e528 digital thermostat requires configuration to work
effectively. The most basic configuration is "binding" the room to
the Room ID (usually the room number) to avoid cross
communication between devices. (For commissioning of complex
systems, please refer to the property specific commissioning
document). Room IDs are 5 digit numbers (X YY ZZ, with zeros
as placeholders where needed) ranging from 1 to 65535. To set
Room ID
Enter Service Mode:
Press and hold °F/°C
Press and release OFF/AUTO
Press and release DISPLAY
Release °F/°C
Go to
(Room ID)
rid
Copyright 2013 INNCOM by Honeywell
Technical Specifications
Power Requirements
Relay Contact Rating
Triac Relay Contact
Rating
Recommended Wire
Size
Thermostat
Measurement Range
Outdoor Air
Temperature
Display Resolution
Standard Deadband
°C/°F Display
a
Ambient Operating
Ambient Storage
Dimensions
Shipping Weight
Approvals
b
Load Specifications
Voltage
Heat Relay K4-5
Cool Relay K4-5
High Fan Relay K1
Medium Fan Relay K2-3 3 amps
Low Fan Relay K2-3
FCC Statement
This device complies with part 15 of the FCC Rules. Operation is
subject to the following two conditions: (1) This device may not
cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause
undesired operation.
Press OFF/AUTO. Default Room ID 65535 will scroll
Set highest digit (0–6) using the UP/DOWN arrows. Press
DISPLAY
Set middle 2 digits (0–99). Press DISPLAY
Set lowest 2 digits (0-99). Press DISPLAY. The new number
will scroll across LCD. The e528 will return to the menu list
24 VAC at 50/60 Hz, 2.4 VA (e528-9xx)
100–277 VAC at 50/60 Hz, 2.4 VA (e528-8xx)
See table below
50m at minimum, 250m at maximum (e528-
4xx)
18 gauge
33–99 °F (1–37 °C)
0–99 °F (-18–37 °C)
Whole degree F, 0.5 °C (0.1 °F in test mode)
2 °F (1 °C) between heating and cooling
Toggle Button located on front display
41–149 °F (5–65 °C), 0–95% RH noncondensing
33–149 °F (1–65 °C)
(HWD) 4.74.71.2in. (12012030mm)
0.6lb (0.27kg)
UL listed #873, CAN/CSA C22.2 No. 24-93 File
#E202540/Part 15 of the FCC Rules
MODEL
e528-A3L6
24VAC
3 amps
125-277VAC
General purpose
3 amps
125-277VAC
General purpose
3 amps
125-277VAC
General purpose
125-277VAC
General purpose
3 amps
125-277VAC
General purpose
e528-B1L6
100-277VAC
240 VA PD
240 VA PD
3.6 FLA
21.6 LRA
2.2 FLA
13.2 LRA
2.2 FLA
13.2 LRA