Powerware PowerPass 9125 User Manual page 33

Distribution module pdm, for use with two-in-one 5000/6000 va
Hide thumbs Also See for PowerPass 9125:
Table of Contents

Advertisement

Table 3. PDM Wiring Specifications
Terminal
Terminal
Position
PPDM EURO HW
1
Input Line 1
2
Input Line 2/N
3
Output 230–240V (Isolated)
4
Output 115–120V
5
Output Neutral
6
Output Line 1, 230–240V
7
Output Line 2/N, 230–240V
E4
Input Earthing
E5
Output Earthing
2
*Use 2.0 mm
(14 AWG) 75_C copper wire minimum.
11.
12.
Powerware
9125 Two-in-One (5000/6000 VA) PDM User's Guide
®
Output +120V
Output -120V
Input L2
Input L1
Input
Ground
E4
1
2
Figure 13. PPDM HW Model Terminal Block
PDM Wire Function
PPDM HW
Input Line 1
Input Line 2
Output -120V
Output +120V
Output Neutral
Output Line 1, 208–240V
Output Line 2, 208–240V
Input Ground
Output Ground
Replace the wiring access cover and the conduit landing plate.
Plug the input and output cords of the PDM into the input and
output power connectors on the UPS rear panel.
Output Neutral
Output Line 1, 208
Output Line 2, 208
3
4
5
6
7
E5
Terminal Wire
Terminal Wire
Size Rating*
2
2
2–17 mm
(14–6 AWG)
(14–6 AWG)
2
2–5 mm
(14–10 AWG)
2
8 mm
8 mm
(8 AWG)
2
17 mm
(6 AWG)
Rev B www.powerware.com
S
Installation
240V
240V
Output
Ground
Tightening
Tightening
Torque
1.8 ±0.22 Nm
(16 ±2 in lb)
(16 ±2 in lb)
2.26 ±0.22 Nm
(20 ±2 in lb)
2.82 ±0.22 Nm
2.82 ±0.22 Nm
(25 ±2 in lb)
3.95 ±0.22 Nm
(35 ±2 in lb)
27