Installation
Table 1. Plug-Receptacle PDM Input/Output Voltage Settings
PPDM L6-30, and PPDM L6-20 Models
Input Voltage
Input Voltage
(from UPS)
PPDM L5-30 Models
Input Voltage
Input Voltage
(from UPS)
PPDM L14-30 Models
Input Voltage
Input Voltage
(from UPS)
PPDM L6-30&L14-30 Models
Input Voltage
Input Voltage
(from UPS)
18
Powerware
9125 Two-in-One (5000/6000 VA) PDM User's Guide
®
208V Switch Position
(HV/LV)
208
208/120
220
220/126
230
230/131
240
240/136
208V Switch Position
208
120
220
126
230
131
240
136
208V Switch Position
(L14-30R/5-15R)
208
240/120
220
252/126
230
262/131
240
272/136
208V Switch Position
(L6-30R/L14-30R/5-15R)
208
208/240/120
220
220/252/126
230
230/262/131
240
240/272/136
PDM Output Voltage
Default 240V Switch Position
(HV/LV)
208/104
220/110
230/115
240/120
PDM Output Voltage
Default 240V Switch Position
104
110
115
120
PDM Output Voltage
Default 240V Switch Position
(L14-30R/5-15R)
208/104
220/110
230/115
240/120
PDM Output Voltage
Default 240V Switch Position
(L6-30R/L14-30R/5-15R)
208/208/104
220/220/110
230/230/115
240/240/120
Rev B www.powerware.com