Installation
EBM Installation
A small amount of arcing may occur when connecting an EBM to the UPS. This
is normal and will not harm personnel. Insert the EBM cable into the UPS
battery connector quickly and firmly.
If you are installing the optional EBM(s), use the following steps:
1.
2.
3.
4.
Battery Circuit
Breaker
Battery Circuit
Breaker
16
Powerware
9125 Two-in-One (5000/6000 VA) PDM User's Guide
®
C A U T I O N
Verify that all battery circuit breakers are in the OFF (O)
position (see Figure 6).
Plug the EBM cable into the UPS battery connector.
If additional EBMs are to be installed, plug the EBM cable of the
second cabinet into the battery connector on the first EBM.
Repeat for each additional EBM. Up to four EBMs may be
connected to the UPS.
Continue to the following section, "Plug-Receptacle PDM
Installation" or "Hardwired PDM Installation" on page 23.
Figure 6. Typical EBM with PDM Installation
UPS Battery
Connector
EBM Cable
EBM Battery
Connector
Rev B www.powerware.com