Download Print this page

Product Description; Technical Data; Installation - Danfoss CCR2 Installation Manual

Disinfection process control & temperature registration

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
Installation Guide
ENGLISH
1.

Product description

2.

Technical data

3.

Installation

4.
Switching the control on
Heating Solutions
CCR2
The CCR2 is a control used for optimising the
thermal disinfection process in hot water
systems with functions such as temperature
registration and monitoring circulation hot water
systems. The control is connected to thermo
Temperature sensor (S0, S1 ... S16)
Temperature range (registration)
Measuring accuracy
Inputs: B1 and B2
Number of control valves (risers)
Output signal to actuators (Triac type)
Alarm signal output (Triac type)
Relay output
OC output (Transistor type)
Type of memory card (included)
Maximum memory card
Timer: Real time clock
Ambient temperature
Transport temperature
IP rating
Power supply
Power consumption
Weight
Installation
For easy access, the CCR2 control is installed in
the technical box on DIN rail 35 mm. Box with
DIN rail should be mounted onto the wall (sub -
station or boiler room) as close as possible to the
heat source. DIN rail and box are not included. It
Before switching the control on for the first
time, disconnect all cables and connect a 24 VAC
source to the disconnected power plug. Use a
voltmeter to measure the voltage on the power
cable plug before it is connected to the control.
If the voltage is correct:
1. Read the instructions before you operate the
control
2. Disconnect all cables
3. Connect the power to the transformer (not
connected to CCR2)
4. Turn on the power to the transformer
5. Verified currency - 24 V
6. Connect the cable from the transformer to the
CCR2 input
actuators type TWA - A and remote temperature
sensors PT1000, type ESMB, installed on each
thermostatic circulation valve, type MTCV
(Multifunctional Thermostatic Circulation Valve).
Pt1000, S0- type ESMC / ESM11, S1 ... S16 – type ESMB
–20 °C ... +120 °C
± 0,1 K
Free contact (5 V 1 mA)
16
24 VAC max. 1 A
24 VAC max. 1 A
0 ... 24 VAC/DC max. 1 A
0 ... 20 V DC NPN Open collector max. 200 mA
SD (512 MB factory card, build in CCR2)
2 GB
Built-in battery - service life 10 years
0 ... 50 °C
–10 ... +60 °C
IP 20,
24 VAC
6 VA
0,9 kg
DIN rail 35 mm
is recommended to install the standard 24 VAC
transformer in the same box as CCR2 (not supply).
Do not install (and remove) SD card when the
CCR2 is connected to the current. It must be
switched off (risk of losing data).
The control should display its name and the
software version – CONTROLLER START MENU –
display according to point 5.
Before any plugs are connected to the control's,
input and output connectors:
1. Set all parameters on the control
2. Make sure that there is no external voltage on
the temperature sensor plugs
3. Make sure that the voltage on the relay
contacts is not too high (max. 24 VAC)
VI.D1.E2.1R
5 5
SMT/SI

Advertisement

loading