Danfoss CCR2 Installation Manual page 11

Disinfection process control & temperature registration

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
Installation Guide
Heating Solutions
CCR2
No
LCD Display
INSTALL MENu - FuNCTION DESCRIPTION
56
Cor
Sensor calibration: S0 ... S16 in range: ±9,9 °C
S0 ...
Do not make calibration when sensor cables are shorter than 10 meters.
... °C
For longer cable then 10 meters, used correction factors from table below.
Correction factor
total length
(two - core cable)
in meter
10
15
20
25
30
35
40
45
50
75
100
125
150
Factory setting: 0 °C
57
Rel.Test
Relay test (Triac output)
AuTO – all work automatically
... ... ... .
V1 ... V16 – forced signal for valves output V1 ... V16
Rel C - NO - forced signal for relay C/NO
T1 Out - forced signal for output T1 (open collector)
T2 Out – forced signal (24 VAC) for alarm T2 .
Factory setting: Auto
58
AlertRel
Alarm output (Triac)
StillOn – continuous alarm signal: T2 – 24 VAC
... ...
Pulse – pulse alarm signal 24 VAC every second
Factory setting: Pulse
59
Archiver
Information about data archiving:
...
Never – the feature is switched off,
1 File – data is stored in one file on the SD card,
2 Files – data is stored alternatively in two files to improve write reliability. This function decreases
term of data storage (twice).
Factory setting: 1 File
60
ArchFreq
Data archiving interval. The time can be set to any value between 10 seconds and 4 hours.
...
Factory setting: 1 min
61
DisSourc
Disinfection sources for running disinfection and continuing the process, There are a few
... ... ..
combinations which allow initiation of the process based on one signal or in relation to many needed
signals. Disinfection is initiated when:
S0 – sensor S0 reports a temperature higher than the disinfection temperature
B1 – B1 input shorted to ground,
S0+SCH – sensor S0 reports a temperature higher than the disinfection temperature in the scheduled
time period,
B1+SCH – B1 input shorted to M (ground) in the scheduled time period,
SCH - weekly schedule runs and continues until it is complete, even if schedule was to terminate it,
S/B0+SCH – B1 input shorted to M (fault to frame, ground) or sensor S0 reports a temperature higher
than the disinfection temperature in the scheduled time period,
S0&B0 – B1 input shorted to M and sensor S0 reports a temperature higher than the disinfection
temperature,
S0&B0+SCH - B1 input shorted to M and sensor S0 reports a temperature higher than the disinfection
temperature in the scheduled time period.
Factory setting: S0
62
BMSAdres
CCR2 address in BMS system
Factory setting: 1
63
BMS TYPE
Type of date transmission:
ModBus 96 (9.600)
Mod Bus 19 (19.000)
ModBus 38 (38.400)
FBus
Factory setting: ModBus 96
64
DateForm
Form of date display:
yy - MM - DD – year, month, day
yy - DD - MM – year, day, month
DD - MM - yy – day, month , year
MM - DD - yy – month, day, year
Factory setting: YY - MM - DD
VI.D1.E2.1R
cable cross section
0,5 mm
0,75 mm
1,00 mm
2
2
- 0,2
- 0,1
- 0,1
- 0,5
- 0,3
- 0,2
- 0,4
- 0,3
- 0,2
- 0,5
- 0,3
- 0,3
- 0,6
- 0,4
- 0,3
- 0,7
- 0,5
- 0,4
- 0,8
- 0,5
- 0,4
- 0,9
- 0,6
- 0,5
- 1,0
- 0,7
- 0,5
- 1,5
- 1,0
- 0,8
- 2,0
- 1,4
- 1,0
- 2,5
- 1,7
- 1,3
- 3,0
- 2,0
- 1,5
1,5 mm
2
2
- 0,1
- 0,1
- 0,1
- 0,1
- 0,2
- 0,2
- 0,2
- 0,2
- 0,3
- 0,4
- 0,5
- 0,6
- 0,8
SMT/SI