13. Temperature set in the circulation risers and disinfection time:
CCR2 ModBus protocol details
Data type : Coil [bool]
Data type Register [integer]
Baud rate:
14
SMT/SI
CCR2
Temperature
Time setting for thermal disinfection
of disinfection
in: hour ... Minute ...
[ °C]
Minimum
required
50
6 h 20 minute
51
6 h 10 minute
52
4 h 00 minute
53
2 h 00 minute
54
1 h 00 minute
55
0 h 50 minute
56
0 h 40 minute
57
0 h 20 minute
58
0 h 15 minute
59
0 h 15 minute
60
0 h 14 minute
61
0 h 13 minute
62
0 h 12 minute
63
0 h 12 minute
64
0 h 11 minute
65
0 h 11 minute
Coil No.
MB_CoilOut [0]
MB_CoilOut [1]
MB_CoilOut [2 ... 9]
MB_CoilOut [10 ... 17]
MB_CoilOut [18 ... 25]
MB_CoilOut [26 ... 33]
MB_CoilOut [34 ... 41]
MB_CoilOut [42 ... 49]
MB_CoilOut [50 ... 57]
MB_CoilOut [58 ... 65]
MB_CoilOut [66]
MB_CoilOut [67]
MB_CoilOut [68]
MB_CoilOut [69]
MB_CoilOut [70]
Register No.
MB_RegisterOut [0 ... 8]
MB_RegisterOut [9 ... 16]
MB_RegisterOut [17 ... 24]
MB_RegisterOut [25 ... 32]
MB_RegisterOut [33]
MB_RegisterOut [34]
MB_RegisterOut [35]
MB_RegisterOut [36+0 ... 7] - control signal (opening) in % for valve in risers : 1 ... 8
MB_RegisterOut [44+0 ... 7] - control signal (opening) % for valve in riser: 9 ... 16
data bits
stop bits
9.600
8+1
19.200
8+1
38.400
8+1
VI.D1.E2.1R
Temperature
of disinfection
[ °C]
Maximum
recommended
7 h 30minute
7 h 20 minute
5 h 50 minute
4 h 00 minute
2 h 00 minute
2 h 00 minute
1 h 20 minute
1 h 00 minute
0 h 50 minute
0 h 45 minute
0 h 40 minute
0 h 35 minute
0 h 30 minute
0 h 28 minute
0 h 27 minute
0 h 26 minute
Description
- disinfection permitted
- disinfection in progress
- open valves ( 0 ... 7)
- risers with open valves (riser: 8 ... 15)
- riser with disinfection error (riser: 0 ... 7)
- riser with disinfection error (riser 8 ... 15)
- riser with finished disinfection, success (riser: 0 ... 7)
- riser with finished disinfection, success (riser: 8 ... 15)
- riser in disinfection group (riser: 0 ... 7)
- riser in disinfection group (riser: 8 ... 15)
- alarm
- disinfection in progress when TS0 is achieved
- permission to run next CCR
- status of binary input : B1
- status of binary input : B2
Description
- temperature sensors S0 ... S8 (8000 <=> 80 °C)
- temperature sensors S9 ... S16 (8000 <=> 80 °C)
- time needed to finished disinfection for risers 1 ... 8 [in minutes ]
- time needed to finished disinfection for risers 9 ... 16 [in minutes]
- selected disinfection time
- degree of disinfection progress when system is divide for group
- number of risers in group
parity
N
N
N
Time setting for thermal disinfection
in: hour ... Minute ...
Minimum
required
recommended
66
0 h 10 minute
67
0 h 9 minute
68
0 h 8 minute
69
0 h 7 minute
70
0 h 6 minute
71
0 h 6 minute
72
0 h 6 minute
73
0 h 5 minute
74
0 h 4 minute
75
0 h 3 minute
76
0 h 3 minute
77
0 h 2 minute
78
0 h 2 minute
79
0 h 2 minute
80
0 h 2 minute
Heating Solutions
Maximum
0 h 25 minute
0 h 25 minute
0 h 22 minute
0 h 21 minute
0 h 20 minute
0 h 18 minute
0 h 14 minute
0 h 12 minute
0 h 10 minute
0 h 10 minute
0 h 10 minute
0 h 9 minute
0 h 8 minute
0 h 6 minute
0 h 6 minute