HDL BUSPRO SB-DN-HVAC User Manual page 9

Air-condition controller
Table of Contents

Advertisement

User Manual
SB-DN-MAC01.331
6.2.2.3.1 Ac model configuration types
There two different modes for the AC model settings regarding the wiring
diagram:-
a) Normal Mode: this mode is the default mode and its correspondent to this module's
default wiring diagram, below is the normal wiring for this module:-
Default wiring: Relay-1=Cooling, Relay-2=Heating, Relay-3=Dehumidification.
b) Complex Mode: this mode is only used when the wiring is not the default wiring so you
can optimize and configure the module according to your own wiring.
For example: suppose that relay#1 is heating, relay#2 is dehumidification and relay#3 is
cooling, in this case we need to make some modification in the Complex mode as the
below figure shows.
Steps:
To modify HVAC complex settings according to specific wiring
a) Select Complex mode
b) Double click on "HVAC setting" table to modify the settings and change the settings in
the pop-up window.
Relay power restore:
if this is selected, this module will recover each mode's status
before power off.
P.s:
this function is only assured when the mode is relay and not for HVAC as below
screenshot shows.
2) Compressor protection
AC controller – User Manual