Power Consumption - Bosch PRAESENSA Installation Manual

Public address and voice alarm system
Hide thumbs Also See for PRAESENSA:
Table of Contents

Advertisement

40
en | System composition
5.4.3

Power consumption

The following table gives an overview of the power demand of the PRAESENSA devices for the
different operating conditions.
Device
PRA-SCL
PRA-CSLD /
PRA-CSLW
PRA-AD604
PRA-AD608
PRA-ES8P2S
PRA-MPS3
2019.11 | V1.00 |
Device elements
System controller
+ per active RJ45 port
Call station
+ per active RJ45 port
+ per extension PRA-CSE
+ with alarm option
Amplifier (sleep)
Amplifier (snooze)
Amplifier (active, idle)
Amplifier (active, low power)
Amplifier (active, full power)
+ per active RJ45 port
Amplifier (sleep)
Amplifier (snooze)
Amplifier (active, idle)
Amplifier (active, low power)
Amplifier (active, full power)
+ per active RJ45 port
Ethernet switch
+ per active RJ45 port
+ per active SFP port
+ PoE load
Multifunction power supply
+ per active RJ45 port
+ per active SFP port
Installation manual
Power
Power from
consumption
battery [W]
[W]
3.9
4.2
0.4
0.5
4.2
5.0
0.5
0.6
0.1
0.1
1.2
1.5
6.0
6.0
8.0
8.5
32
39
52
64
220
250
0.4
0.4
6.0
6.0
8.4
9.2
38
48
70
88
242
274
0.4
0.4
7.0
8.4
0.4
0.5
0.7
0.8
load
1.2 x load
5.2
5.2
0.4
0.4
0.7
0.7
Bosch Security Systems B.V.
PRAESENSA
Current
from
battery [A]
0.35
0.04
0.42
0.05
0.01
0.12
0.50
0.71
3.25
5.33
20.83
0.03
0.50
0.77
4.00
7.33
22.83
0.03
0.70
0.04
0.07
0.1 x load
0.43
0.03
0.06