Honeywell 2MLF-AV8A User Manual page 41

Analog input module
Table of Contents

Advertisement

2.
If an error occurs in the filter setting value, the default filter setting value 1 is saved.
2MLF-AV8A
Analog input range: DC -10 ~ 10V, digital output range: 0 ~ 16000.
If analog input value changes –10V ~ 10V (0 ~ 16000), the filter output value, based
on α value, is as specified below.
α value
*1) 0.01
*2) 0.5
*3) 0.99
*1) 16000 output after about 4 scans
*2) 16000 output after about 22 scans
*3) 16000 output after about 1491 scans (372.75ms for 1 channel Run)
2MLF-AC8A
Analog input current range: DC 0 ~ 20mA, digital output range: 0 ~ 16000.
If analog input value changes 0mA ~ 10mA (0 ~ 8000), the filter output value, based
on α value, is as specified below.
α value
*1) 0.01
*2) 0.5
*3) 0.99
R200
Analog Input Module 2MLF-AV8A, AC8A User's Guide
September 2010
Filter Output Value
1 scan
2 scan
0
15840
15998
0
8000
12000
0
160
318
Filter output value
1 scan
2 scan
0
7920
7999
0
4000
6000
0
80
159
Honeywell
2. Specifications
Remarks
3 scan
1% inclined toward previous
15999
value
50% inclined toward previous
14000
value
99% inclined toward previous
475
value
Remarks
3 scan
1% inclined toward previous
7999
value
50% inclined toward previous
7000
value
99% inclined toward previous
237
value
2.4. Functions
41

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

2mlf-ac8a

Table of Contents