6. Programming
6.4. Application program examples
6.4
Application program examples
Program to compare A/D conversion values
The following figure shows system configuration.
Details of initial setting
No.
Item
1
Used CH
Input voltage
2
range
3
Output data range
4
Filter process
CH0 filter
5
constant
6
Average process
Average
7
processing
method
8
Average value
120
Analog Input Module 2MLF-AV8A, AC8A User's Guide
Details of Initial
Setting
CH0, CH2, CH4
-10 ~ 10V
0 ~ 16000
CH0
50
CH2, CH4
Frequency average:
CH2
Time average: CH4
Frequency average
value: 100 (times)
Time average value:
200 (ms)
Honeywell
Internal
Value to Write on
Memory
Internal Memory
Address
0
'h0015' or '21'
1
'hFFFF' or '65535'
2
'h0000' or '0'
3
'h0001' or '1'
4
'h0032' or '50'
12
'h0014' or '20'
13
'h0010' or '16'
16
'h0064' or '100'
18
'h00C8' or '200'
R200
September 2010