CPU module cannot read A/D conversion value
CPU module cannot read A/D conversion
Channel Enable/Disable set correctly?
Target CH's input terminal wiring is
Contact nearest Honeywell office or
authorized service engineer
Mismatch between analog input value and digital output value
Mismatch between analog input value
and digital output value?
Every CH analog input type (4-20 or 0-
20mA) set correctly.
Analog input terminal wiring is correct?
Contact nearest Honeywell office or
authorized service engineer
R200
Analog Input Module 2MLF-AV8A, AC8A User's Guide
September 2010
value.
correct?
Honeywell
Set the Enable/Disable status correctly for each
channel.
Refer to section on Installation and Wiring for
proper wiring.
Set the analog input type correctly.
Refer section on Installation and Wiring
for proper wiring.
7. Troubleshooting
7.2. Troubleshooting
133