2.4 Features

LCD display showing the status of each transducer and relay
External keypad for user selection of the transducer/alarm display and setting the configuration (password protected)
Three RS-485 digital input channels – 192 addressable sensors
Up to 8 control zones can be defined
Each zone can be controlled based on transducer signals and/or time of day
Comes standard with four onboard 10A, 240 VAC SPDT Dry Contact relays
Up to four optional onboard expansion relays available
Up to 2 additional remote relays available
Each relay is configurable with a delay before activation and minimum on time
Fail-safe operation can be implemented
Lockable NEMA 4X type enclosure
Modular input and output connectors
Ethernet connection for BACnet output (BACnet IP)
USB connection
Compatible with Macurco Commercial 6-Series gas detectors, MRS-485 adapter, Horn & Strobe Combo
Four 24VDC Drivers for external Horn and Strobe
Three 4-20mA output
ETL Listed to UL 2017

2.5 Specifications

Size:
Weight:
Enclosure:
Operating Temperature:
Operating Humidity:
Power Input:
Relay Rating (4):
LCD Display:
Status Indicators (LED):
Audible indicator:
External Drivers (4):
Relay on Delay:
Relay Minimum Run Time:
REV – 1.3.1
13.0" x 10.0" x 2.75"
12.4 lb. (5.6 kg)
NEMA 4X rated
32° to 104°F (0° to 40°C)
0% to 95% RH non-condensing
100 – 240 VAC, 1 Amp, 50/60 Hz, single phase
SPDT, 120/240 VAC, 10 A Max (resistive)
320 x 240 Pixels Graphic LCD Display with backlight
Power/Trouble, Hush, Warning/ALARM, and Relay
Internal buzzer, 90 dBA at 1ft
24VDC, maximum 250 mA
0 – 99 minutes in 1 second increments
0 – 99minutes in 1 second increments
[34-8708-4770-7 ]
7 |
P a g e