Operating Parameters - Johnson Controls RJ H Series Installation Operation & Maintenance

Water source heat pump
Table of Contents

Advertisement

Operating Parameters

Single Speed Models
Entering Water
Water Flow
Temp °F
GPM/Ton
1.5
50
3.0
1.5
70
3.0
1.5
90
3.0
Entering Water
Water Flow
Temp °F
GPM/Ton
1.5
30
3.0
1.5
50
3.0
1.5
70
3.0
Note: Cooling performance based on entering air temperatures of 80º F DB, 67º F WB.
Heating performance based on entering air temperature of 70º F DB.
Suction
Discharge
Pressure PSIG
Pressure PSIG
133 - 148
205 - 225
129 - 144
185 - 205
139 - 154
280 - 300
137 - 152
250 - 270
143 - 158
360 - 380
141 - 156
330 - 350
Suction
Discharge
Pressure PSIG
Pressure PSIG
73 - 79
279 - 304
79 - 85
285 - 310
103 - 109
308 - 333
110 - 116
315 - 340
140 - 146
330 - 365
146 - 153
340 - 375
Cooling -- No Hot Water Generator
009-070
009-070
Water Temp
Superheat
Subcooling
17 - 26
10 - 14
20 - 29
7 - 11
8 - 11
8 -12
9 - 12
7 - 11
8 - 11
9 - 13
9 - 12
8 - 12
Heating -- No Hot Water Generator
009-070
009-040
Superheat
Subcooling
Subcooling
7 - 13
2 - 6
8 - 14
2 - 6
8 - 12
4 - 8
9 - 13
4 - 8
10 - 14
7 - 11
10 - 14
7 - 11
47
RJ SERIES INSTALLATION MANUAL
Air Temp Drop
Rise °F
°F DB
18 - 22
18 - 22
8 - 10
18 - 22
18 - 22
18 - 22
8 - 10
18 - 22
18 - 22
16 - 20
8 - 10
16 - 20
048
060-070
Water Temp
Subcooling
Drop °F
11 - 15
4 - 8
11 - 15
4 - 8
13 - 17
6 - 10
8 - 11
13 - 17
6 - 10
14 - 18
9 - 13
11 - 14
14 - 18
9 - 13
7 - 10
Air Temp Rise
°F DB
7 -10
18 - 24
3 - 6
20 - 26
20 - 26
4 - 7
22 - 28
26 - 32
28 - 34

Advertisement