Model RSH/RSV SERIES Model RSH/RSV SERIES -410A WATER SOURCE HEAT PUMPS Update Form 145.16-IOM2 (0611) MODEL RSH/RSV R-410A WATER SOURCE HEAT PUMP WATER SOURCE HEAT PUMP INSTALLATION AND OPERATION INSTRUCTIONS INSTALLATION AND OPERATION INSTRUCTIONS INSTALLATION AND OPERATION INSTRUCTIONS...
All wiring must be in accordance with published specifications and must be performed ONLY All wiring must be in accordance with published specifications and must be performed ONLY by qualified service personnel. Johnson Controls will not be responsible for damages/problems qualified service personnel. Johnson Controls will not be responsible for damages/problems qualified service personnel.
Supply Air Options N = Microprocessor Control with CSS Interface S = Straight-Thru (Horizontal Only) B = Back Discharge (Horizontal Only) T = Top Discharge (Vertical Only) Return Air/Unit Orientation L = Left Hand R = Right Hand JOHNSON CONTROLS...
FORM 145.16-IOM2 (0611) CHANGEABILITY OF THIS DOCUMENT In complying with Johnson Controls policy for continu- It is the responsibility of operating/service personnel as ous product improvement, the information contained in to the applicability of these documents to the this document is subject to change without notice.
Heat Pump models protection can be disabled. Heat Pump models feature a pilot operated, sliding piston type, 4 feature a pilot operated, sliding piston type, 4- way reversing valve with a replaceable magnetic aceable magnetic solenoid coil. JOHNSON CONTROLS...
GRAVITY OF THE UNIT BY PERFORM- ING A TEST LIFT. LIFTING AN UNBAL ING A TEST LIFT. LIFTING AN UNBAL- ANCED UNIT CAN CAUSE PERSONAL ANCED UNIT CAN CAUSE PERSONAL INJURY OR EVEN DEATH. INJURY OR EVEN DEATH. JOHNSON CONTROLS...
1) Nominal Capacity calculated in accordance with ARI / ISO Standard 13256-1 for Water Loop Application OPERATING LIMITS COOLING HEATING Min. Entering Water Max. Entering Water Units are capable of operation with an entering fluid temperature range of 20 F to 110 JOHNSON CONTROLS...
Units should be or tee upstream of the first outlet connection for supported from the holes in the rail extensions at good sound attenuation. the four corners, using steel threaded rods JOHNSON CONTROLS...
18 Ga. thermostat and the unit should be 18 Ga. minimum. Appropriate JCI room thermostats can minimum. Appropriate JCI room thermostats can be ordered as an optional accessory for delivery accessory for delivery with the units if desired. JOHNSON CONTROLS...
To be available, a compressor must not be requested operation is available and, if so, which locked-out due to a high-pressure switch; low- components to energize. pressure switch; condensate overflow switch; freezestat trip; and the anti-short cycle delay (ASCD) must have elapsed. JOHNSON CONTROLS...
Condensate compressor, initiate the ASCD, and stop the fan. Overflow lock-out. If the call for cooling is still present at the conclusion of the ASCD, the microprocessor control will re-energize the compressor. JOHNSON CONTROLS...
1 to 64 seconds. The random number generator seed is determined by a fixed seed programmed at the factory combined with the serial number, model number, and the hours of compressor run time of the unit. JOHNSON CONTROLS...
Compressor Held OFF due to Low Voltage 14 Flashes EEPROM Storage Failure (Control Failure) 15 Flashes Condensate Overflow Switch – Compressor Lock out 16 Flashes Coaxial Freeze Thermostat – Compressor Lock out 1. These flash codes do not represent alarms. JOHNSON CONTROLS...
1835 1805 1770 1730 1680 1620 Units are shipped pre-wired for Medium speed. All airflow ratings are at lowest voltage rating of dual rating (ie. 208 volt) Airflow ratings include resistance of wet coil and clean air filters. JOHNSON CONTROLS...
An external sweat if subjected to low water temperatures. d to low water temperatures. P-trap is not necessary. Insulate these lines as necessary to prevent Insulate these lines as necessary to prevent condensation damage. JOHNSON CONTROLS...
Verify that the low voltage wiring between indicating a high-pressure lock-out. out. the unit and the thermostat is correct. the unit and the thermostat is correct. Verify that shipping bolt (on RSH units Verify that shipping bolt (on RSH units only) has been removed JOHNSON CONTROLS...
Page 19
11) After five minutes, verify heating mode operation by checking for warm air discharge at the supply air outlet. 12) Adjust the thermostat to maintain the desired space temperature. 13) Check the unit for unusual vibrations, noises, leaks, etc. JOHNSON CONTROLS...
The Manufacturer will replace the defective cannot anticipate or control the many different parts within 21 days after the return to The conditions under which The Manufacturer's Manufacturer of such defective part or parts information and products may be used. JOHNSON CONTROLS...