Electronic Thermostat Installation; Auxiliary Heat Ratings - Johnson Controls RJ H Series Installation Operation & Maintenance

Water source heat pump
Table of Contents

Advertisement

Electrical Connections cont.
Pump Wiring
See Figure 14 for electrical connections
from control box to pumps.
Electronic Thermostat
Position the thermostat subbase against the wall so that it is level and the thermostat wires
protrude through the middle of the subbase. Mark the position of the subbase mounting
holes and drill holes with a 3/16-inch bit. Install supplied anchors and secure base to the
wall. Thermostat wire must be 8-conductor, 18-AWG wire. Strip the wires back 1/4-inch
(longer strip lengths may cause shorts) and insert the thermostat wires into the connector
as shown. Tighten the screws to insure secure connections. The thermostat has the same
type connectors, requiring the same wiring. See instructions enclosed in the thermostat for
detailed installation and operation information.
Note: DIP switch SW2-8 is required to be in the "OFF" position for the control to operate with
FaultFlash or ComforTalk thermostats. SW2-8 in the "ON" position configures the control to
operate with typical thermostats (continuous lockout signal). There must be a wire connecting Y2 on the microprocessor controller to 2nd
stage compressor on the thermostat for proper operation.

Auxiliary Heat Ratings

KW
Model
208V
230V
EAS(H)4
2.9
3.8
EAM(H)5
3.6
4.8
EAM(H)8
5.7
7.6
EAM(H)10
7.2
9.6
EAL(H)10
7.2
9.6
EAL(H)15
10.8
14.4
EAL(H)15-3
10.8
14.4
EAL(H)20
14.4
19.2
"H" is used in part number for horizontal units
Figure 14: Pump Wiring 208-230/60/1
TO PUMP
BTU/HR
Stages
208V
230V
1
9,700
12,900
1
12,300
16,300
2
19,400
25,900
2
24,600
32,700
2
24,600
32,700
3
36,900
49,100
3
36,900
49,100
4
49,200
65,500
L1
Min
CFM
009-012
015
250
450
550
650
1100
1250
1250
1500
17
RJ SERIES INSTALLATION MANUAL
L2
Figure 15: Thermostat Wiring
R
24VAC (Hot)
C
24VAC (Common)
Y1
Compressor (1st Stage)
Y2
Compressor (2nd Stage)
W
Aux. Heat
O
Reversing Valve
G
Blower Relay
L
System Monitor
RJ Series Compatibility
018
022
026 - 030 036 - 049 060 - 072

Advertisement

Table of Contents
loading

Table of Contents