FX10 Advanced Control Overview
The Johnson Controls FX10 board is specifically designed for
commercial heat pumps and provides control of the entire unit
as well as input ports for Open N2, LonTalk, BACnet (MS/TP @
19,200 Baud rate) communication protocols as well as an input
port for a user interface. The user interface is an accessory item
that can be used to aid in diagnostics and unit setup. A 16-pin
low voltage terminal board provides terminals for common field
connections. The FX10 Control provides:
Operational sequencing
High and low-pressure switch monitoring
General lockout
Low Water Coil Temperature
Condensate overflow sensing
Lockout mode control
Emergency shutdown mode
Random start and short cycle protection
Short Cycle Protection
Allows a minimum compressor "off" time of four minutes and a
minimum "on" time of two minutes.
Random Start
A delay of 1 to 120 seconds is generated
after each power-up to prevent simultaneous startup of all units
within a building after the release from an unoccupied cycle or
power loss.
Emergency Shutdown
A field-applied dry contact can be used to place the control into
emergency shutdown mode. During this mode, all outputs on the
board are disabled.
Low Water Coil Temperature Limit
Field selectable for 15° or 30°F (-9° or -1°C)
Installation Options
Standalone controlled by standard room thermostat
Standalone with a Zone Temperature Sensor (must
have user interface to change set points beyond the
allowed +/- 5°F)
Integrated into BAS by adding communication module
Accessory Outputs
Quantity 2. One cycled with fan, other with compressor.
User Interface
4 x 20 backlit LCD.
Main FX 10 Board
Optional Plug-in Communication Modules -
(compatible with standard BAS protocols)
Open N2
LonTalk
BACnet (MS/TP @ 19,200 Baud rate)
Display
Requires DLI Card/Kit. Up to 2 displays, either 1 local and 1
remote, or 2 remote. (A 2-display configuration requires identical
displays.) Local display can be up to 3 meters from the controller,
power supply, and data communication. Remote display can be
up to 300 meters from the controller. Remote display must be
independently powered with data communication done via 3 pole
shielded cable.
Control Timing & Fault Recognition Delays
Lead compressor "ON" delay ............................................90 seconds
(not applicable for single compressor models)
Minimum compressor "ON" time ...........................................2 minutes
(except for fault condition)
Short cycle delay ..................................................................5 minutes
Random start delay ......................................................0-120 seconds
High pressure fault ............................................................. <1 second
Low pressure fault .............................................................30 seconds
Freeze detection fault ........................................................30 seconds
Condensate overflow fault .................................................30 seconds
Low pressure fault bypass ....................................................2 minutes
Freeze detection fault bypass...............................................2 minutes
35
RJ SERIES INSTALLATION MANUAL