INSTALLATION MANUAL
R-410A Outdoor Split-System
Heat Pump
Models: 14 SEER -
YHE, TH4, THE, RHP14L Series
1.5 to 5 ton - Single-Phase and Three-Phase
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Unit installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Indoor expansion device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Evacuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
System charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Typical installation clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Alternative installation clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Installation of vapor line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Underground installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Heat protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
TXV installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
TXV bulb and equalizer line installations . . . . . . . . . . . . . . . . . . . . . . 6
Proper bulb location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Outdoor unit swing away control box . . . . . . . . . . . . . . . . . . . . . . . . 19
Maximum / minimum operating limit conditions . . . . . . . . . . . . . . . . . 2
R-410A saturation properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
stallations for listed equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.5 ton subcooling charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
12 ton subcooling charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.5 ton subcooling charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3 ton subcooling charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.5 ton subcooling charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4 ton subcooling charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5 ton subcooling charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Section I: General
The outdoor units are designed to be connected to a matching indoor
coil with sweat connect lines. Sweat connect units are factory charged
with refrigerant for a nominal sized matching indoor coil plus 15 ft of
field-supplied lines.
Matching indoor coils can be used with a thermostatic expansion valve
(TXV). Refer to the Tabular Data Sheet or to the Technical Guide for the
proper selection.
Section II: Safety
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
Johnson Controls Ducted Systems
List of sections
Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
System start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
System operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Instructing the owner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Start-up sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
List of figures
(single-phase and three-phase) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Heat pump flow diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Demand defrost control module . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Defrost operation curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
for models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
List of tables
1.5 ton heating charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2 ton heating charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.5 ton heating charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3 ton heating charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4 ton heating charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5 ton heating charts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
TEST input functionality with Y . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
TEST input functionality without Y . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Status code display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property dam-
age.
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or maintenance
can cause injury or property damage. Refer to this manual for assis-
tance or for additional information, consult a qualified contractor,
installer or service agency.
WARNING
!
6152307-UIM-B-1022
®

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the YHE Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Johnson Controls YHE Series

  • Page 1: Table Of Contents

    Understand and pay particular attention to the signal words DANGER, can cause injury or property damage. Refer to this manual for assis- tance or for additional information, consult a qualified contractor, WARNING, or CAUTION. installer or service agency. Johnson Controls Ducted Systems 6152307-UIM-B-1022...
  • Page 2: Unit Installation

    Piping Application Guide (P/N 247077). Never leave a suction-line drier in the system longer than 50 h of run time. Johnson Controls Ducted Systems...
  • Page 3: Typical Installation Clearances

    6152307-UIM-B-1022 Figure 1: Typical installation clearances Figure 2: Alternative installation clearances Johnson Controls Ducted Systems...
  • Page 4: Installation Of Vapor Line

    Replacements for the liquid line drier must be exactly the same as marked on the original factory drier. See Source 1 for O.E.M. replacement driers. Figure 3: Installation of vapor line R-410A filter drier Source 1 part number Apply with models S1-32649682000 Johnson Controls Ducted Systems...
  • Page 5: Underground Installation

    3/4 ounce of refrigerant will be lost each time a standard man- 2. Braze the liquid line to the liquid valve at the outdoor unit. Be sure ifold gauge is connected. to wrap the valve body with a wet rag. Allow the nitrogen to con- tinue flowing. Johnson Controls Ducted Systems...
  • Page 6: Indoor Expansion Device

    Hand tighten the liq- 7. Pass the TXV temperature sensing bulb through the suction line uid line, and apply an additional 1/4 turn to seal. split grommet in the access panel. Johnson Controls Ducted Systems...
  • Page 7: Evacuation

    This may cause damage to the compressor or other components. Recover and weigh System Charge into an appropriate recovery cylinder for any instances requiring evacuation. Johnson Controls Ducted Systems...
  • Page 8: Required Subcool Adjustment Levels For Downflow And Horizontal-Right In

    339 (7) 343 (7) 357 (6) 359 (6) 362 (7) 367 (7) 390 (7) 391 (7) 395 (7) 399 (7) 423 (7) 424 (7) 429 (7) 432 (7) 456 (7) 456 (7) 462 (8) 465 (8) Johnson Controls Ducted Systems...
  • Page 9 258 (7) 260 (7) 278 (7) 282 (7) 284 (8) 285 (8) 304 (9) 308 (9) 311 (9) 311 (9) 330 (9) 334 (9) 337 (9) 337 (9) 357 (10) 358 (10) 359 (10) 363 (10) Johnson Controls Ducted Systems...
  • Page 10 281 (5) 283 (5) 294 (4) 312 (4) 303 (5) 304 (5) 315 (4) 335 (4) 326 (5) 326 (5) 336 (4) 358 (5) 347 (5) 348 (5) 365 (4) 388 (5) 376 (6) 377 (6) Johnson Controls Ducted Systems...
  • Page 11 386 (6) 388 (6) 494 (5) 493 (5) 498 (5) 501 (6) 417 (7) 415 (7) 417 (7) 418 (7) 523 (5) 522 (5) 526 (5) 530 (6) 448 (7) 445 (7) 447 (7) 449 (7) Johnson Controls Ducted Systems...
  • Page 12 469 (6) 470 (5) 483 (3) 493 (3) 487 (3) 490 (4) 491 (5) 498 (5) 496 (5) 497 (5) 511 (3) 521 (3) 514 (3) 518 (4) 518 (5) 526 (5) 524 (5) 525 (5) Johnson Controls Ducted Systems...
  • Page 13 325 371 418 296 342 Liquid pressure (psig) 345 391 436 321 368 414 294 338 381 275 318 1000 Liquid pressure (psig) 313 358 403 296 342 387 275 318 361 255 294 Suction pressure (psig) Johnson Controls Ducted Systems...
  • Page 14 315 360 405 291 331 1000 Liquid pressure (psig) 337 383 429 317 352 410 293 338 382 275 313 1200 Liquid pressure (psig) 308 353 398 292 337 382 272 316 360 258 295 Suction pressure (psig) Johnson Controls Ducted Systems...
  • Page 15 320 365 409 318 360 1200 Liquid pressure (psig) 352 396 439 326 373 419 292 335 378 304 344 1450 Liquid pressure (psig) 322 364 406 300 346 391 272 315 359 290 329 Suction pressure (psig) Johnson Controls Ducted Systems...
  • Page 16 278 322 366 259 301 1400 Liquid pressure (psig) 328 355 382 283 326 368 262 303 345 248 289 1650 Liquid pressure (psig) 309 335 362 269 312 354 253 293 333 237 278 Suction pressure (psig) Johnson Controls Ducted Systems...
  • Page 17 272 313 355 236 300 1600 Liquid pressure (psig) 308 352 396 286 331 374 257 297 337 235 287 1850 Liquid pressure (psig) 295 337 379 274 318 361 248 287 326 234 275 Suction pressure (psig) Johnson Controls Ducted Systems...
  • Page 18 319 365 412 273 313 1750 Liquid pressure (psig) 355 403 451 330 363 426 303 349 394 261 301 2000 Liquid pressure (psig) 335 383 430 314 347 408 291 335 380 249 290 Suction pressure (psig) Johnson Controls Ducted Systems...
  • Page 19: Outdoor Unit Swing Away Control Box

    3. Replace the control box cover removed in Step 2 of the Field con- 1. Install the proper size weatherproof disconnect switch outdoors and nections power wiring procedures. within sight of the unit. 4. All field wiring to be in accordance with national electrical codes (NEC) and/or local-city codes. Johnson Controls Ducted Systems...
  • Page 20: System Start-Up

    YES on the indoor variable speed air ous testing functions during installation and service. The TEST input handler or furnace control board. connector is shown in Figure 14. The following table summarizes the Johnson Controls Ducted Systems...
  • Page 21: Heat Pump Flow Diagram

    The control shall immediately clear the stored error code array, reset the 6 h PS timer and flash the STA- > 5 TUS LED 6 times (0.1 s ON / 0.1 s OFF) to indicate that the error memory has been cleared. Figure 13: Heat pump flow diagram Johnson Controls Ducted Systems...
  • Page 22: Demand Defrost Control Module

    The control will cause the heat pump unit to operate in the normal heating mode until it determines that a defrost cycle is needed. All defrost timings are based on accumulated compressor run time. Johnson Controls Ducted Systems...
  • Page 23: Defrost Operation Curves

    No call for defrost Time Defrost (6 hour) prevented Defrost prevented from starting INHIBIT CURVE REGION B REGION A No call for Defrost Call for Defrost Time Defrost (6 hour) allowed AMBIENT TEMPERATURE A0144-001 Figure 15: Defrost operation curves Johnson Controls Ducted Systems...
  • Page 24: Instructing The Owner

    SYSTEM OFF and back to HEAT or COOL mode. 2. The TEST terminals are shorted for more than two s. Johnson Controls Ducted Systems...
  • Page 25: Wiring Diagram

    HPS LPS RV RVG C M COIL AMBIENT DEMAND DEFROST BOARD CONTACTOR USE COPPER HIGH VOLTAGE CONDUCTORS COND FAN ONLY 208-230 VAC 60 Hz 1 PHASE SUPPLY 5603866-UWD-A-1118 Figure 16: Wiring diagram - single-phase PSC 208/230 V for models Johnson Controls Ducted Systems...
  • Page 26: Wiring Diagram - Single-Phase Ecm 208/230 V For Models

    HPS LPS RV RVG C M COIL AMBIENT DEMAND DEFROST BOARD CONTACTOR COND FAN RELAY USE COPPER CONDUCTORS ONLY 208-230 VAC 60 Hz 1 PHASE SUPPLY 5603869-UWD-C-0722 Figure 17: Wiring diagram - single-phase ECM 208/230 V for models Johnson Controls Ducted Systems...
  • Page 27: Wiring Diagram - Three-Phase Psc 208/230 V Motor For Models

    HPS LPS RV RVG C M COIL AMBIENT DEMAND DEFROST BOARD HIGH VOLTAGE COND FAN USE COPPER CONDUCTORS ONLY 208-230 VAC 60 Hz 3 PHASE SUPPLY 5603867-UWD-B-0120 Figure 18: Wiring diagram - three-phase PSC 208/230 V motor for models Johnson Controls Ducted Systems...
  • Page 28: Wiring Diagram - Three-Phase Psc 460 V Motor For Models

    HPS LPS RV RVG C M COIL AMBIENT DEMAND DEFROST BOARD HIGH VOLTAGE COND FAN USE COPPER CONDUCTORS ONLY 460 VAC 60 Hz 3 PHASE SUPPLY 5603868-UWD-B-0120 Figure 19: Wiring diagram - three-phase PSC 460 V motor for models Johnson Controls Ducted Systems...
  • Page 29: Wiring Diagram - Three-Phase Ecm 208/230 V And 460 V Motor For Models

    HPS LPS RV RVG C M COIL AMBIENT DEMAND DEFROST BOARD COND FAN RELAY USE COPPER CONDUCTORS ONLY 230/460 VAC 60 Hz 5603870-UWD-C-0722 3 PHASE SUPPLY Figure 20: Wiring diagram - three-phase ECM 208/230 V and 460 V motor for models Johnson Controls Ducted Systems...
  • Page 30 6152307-UIM-B-1022 NOTES Johnson Controls Ducted Systems...
  • Page 31: Start-Up Sheet

    Venting system correctly sized within the limitations of the charts in the installation instructions Intake size No. of 90° elbows No. 0f 45° elbows Length Exhaust size No. of 90° elbows No. 0f 45° elbows Length Page 1 of 2 (9/24/21) Johnson Controls Ducted Systems...
  • Page 32 Explain the importance of regular filter replacement and equipment maintenance. Comments section Page 2 of 2 (9/24/21) Subject to change without notice. Published in U.S.A. 6152307-UIM-B-1022 Copyright © 2022 by Johnson Controls. All rights reserved. Supersedes: 6152307-UIM-A-0921 York International Corp. 5005 York Drive Norman, OK 73069...

This manual is also suitable for:

Th4 seriesThe seriesRhp14l series

Table of Contents