The Settings page opens.
Click on the Basic settings tab.
Enter an individual name for the device. The maximum
length is 20 characters.
Enter the serial number(s) of the installed battery module
(expansion stage element 3/6)
or of the installed battery modules (expansion stage
element 6).
The sequence of the entry can be random.
Click on Apply.
i
Once the correct serial numbers have been entered, the
LED ring indicator changes from red to green.
If the LED continues to be red or to flash with a red light,
the following remedies have to be taken.
Remedy: LED ring flashes red
Error:
The current sensor check failed. Please switch the battery storage
system off and back on again.
If the LED ring continues to flash red after the restart (duration
approx. 3 minutes), check the connection to the current sensor
and the phase assignment.
If the LED ring continues to flash red, please contact VARTA
Storage GmbH.
Subject to modification!
98
The storage system cannot be commissioned
unless the correct serial number(s) of the
battery modules are stated.