The screws for opening the storage cabinet on the left next to the
front door must be accessible.
A minimum clearance of 30 cm must be left above the storage
cabinet. The distance between the wall and the rear of the cabinet
must remain free to enable cooling air to escape from the device
unhindered.
8.3.2

Environmental conditions

The installation location must match a pollution degree 2.
A continuous air exchange, possibly via forced ventilation, e.g.
window, air-conditioning system, ventilation or the like, has always
to be ensured. The distance to the ventilation must be at least
100 cm.
The room temperature always has to be between 5
(optimum +18 °C), the relative humidity must be < 80%.
 Recommendation: well ventilated room without external heat
sources
Sufficient rodent protection must be provided.
Smoking is not allowed at the installation
location!
Subject to modification!
Updated 10/2017

30 °C