An error has occurred if the value for the current (I grid)
hovers between +0.01 and -0.01 at all three phases.
Check the cable connection to the current sensor.
Note: The system may need to have a large load at all three
phases.
Checking the battery modules
Check whether the serial numbers of all installed battery
modules are displayed.
8.10.10 Exiting the password-protected area
Finally, it is necessary to ensure that the customer is unable to
access the password-protected area.
Click on the Logout tab.