8.3

Installation location

The following dimensions and framework conditions have to be
complied with at the installation location.
8.3.1

Dimensions and features

For the room, in which the VARTA element will be installed, a
volume of at least 30 m³ is recommended. A horizontal, even floor
with a minimum surface of 70 cm x 55 cm (width x depth). The floor
must be able to take the load.
Weight of the energy storage system  Chapter 3.6 Technical
parameters.
If necessary, have the statics tested.
The ground, the adjacent walls and ceiling must not
consist of heat-sensitive material.
The distance to the adjacent installations must be approx. 5 cm to
the right and approx. 10 cm to the left. A clear space of approx. 120
cm depth is required in front of the device, in order to carry out
installation and maintenance work via the front door. In order to
secure the means of escape, doors must not swing into this clear
space.
Subject to modification!