Risk Analysis Of The Plant; Important Information On The Emergency Stop Button - Siemens SIMATIC PRO Extension Units KP Series Operating Instructions Manual

System components
Table of Contents

Advertisement

Safety instructions

2.4 Risk analysis of the plant

2.4
Risk analysis of the plant
Note
Risk analysis in an F-system is always required
A risk analysis must be performed for each F-system. The responsibility lies with the
operator of the plant.
The following rules apply to the risk analysis of the plant:
● ISO 12100-1 and ISO 12100-2, General design guidelines for machines
● ISO 13849-1, Safety of machinery - Safety-related parts of control systems - General
principles for design
● ISO 14121-1, Safety of machinery – Risk assessment – Part 1: Principles
The results of the risk analysis leads to the Performance Levels a to e in accordance with
ISO 13849-1, which indicates how the safety-related system components must be designed
if the stop or emergency stop functions are needed locally in a plant segment or globally
throughout the plant and which operating mode is to be used for the devices in a safety-
related plant area.
Take the plant configuration as a whole into consideration in the risk analysis and not just the
individual areas. Additional information on risk analysis and risk mitigation is available at:
"Safety Technology in SIMATIC S7" system manual
(http://support.automation.siemens.com/WW/view/en/12490443)
2.5

Important information on the emergency stop button

Stop functions of Category 0 or 1 according to EN 60204-1
If the emergency stop button is looped as a stop button in the stop circuit of the system, the
following applies:
If a category 0 or 1 stop circuit is implemented, the stop function must be effective
regardless of the operating mode. A category 0 stop must take precedence. Releasing the
emergency stop button must not lead to a dangerous state (see also EN 60204-1,
Section 9.2.5.3).
The stop function is not to be used as a replacement for safety equipment.