Mechanical Stress Tests; Climatic Stress Tests - Siemens 7XV5550-0xA00 Series Manual

Active mini-starcoupler
Table of Contents

Advertisement

2.4

Mechanical Stress Tests

Mechanical tests
Vibration and shock during operation
Vibration
IEC 60255-21-1, class 1
IEC 60068-2-6
Shock
IEC 60255-21-2, class 1
Seismic vibration
IEC 60255-21-2, class 1
IEC 60068-3-3
Vibration and shock during transport
Vibration
IEC 60255-21-1, class 1
IEC 60068-2-6
Shock
IEC 60255-21-2, Klasse 1
IEC 60068-2-27
2.5

Climatic Stress tests

Ambient Temperatures
EN 60068-2-1 and -2-2
Recommended operating temperature
with all fibre optic interfaces in idle state ´OFF´
with all fibre optic interfaces in idle state ´ON´
Limiting temporary (transient) operating
temperature (all interfaces in idle state ´OFF´)
Limiting temperatutre during storage
(with packing from the factory)
Limiting temperature during transport
(with packing from factory)
Humidity
Page 18 from 52
sinusoidal 10 Hz to 60 Hz: ±0,035mm
amplitude.; 60Hz - 150 Hz: 0,5g acceleration
Frequency sweep rate 10 oktave/min
20 cycles in 3 orthogonal axes, half-sinusoidal
Acceleration 5 g, duration 11 ms, 3 shocks in each
direction of 3 orthogonal axes
sinusoidal
1 Hz to 8 Hz: +3,5mm amplitude
(horizontal axis)
1 Hz to 8 Hz: +1,5mm amplitude
(vertical axis)
8 Hz to 35 Hz: 1g acceleration
(horizontal axis)
8 Hz to 35 Hz: 0,5g acceleration
(vertical axis)
Frequency sweep rate 1 octave / min
1 cycle in 3 orthogonal axes
sinusoidal
5 Hz to 8 Hz: ±7,5 mm amplitude;
8 Hz to 150 Hz: 2 g acceleration
Frequency sweep rate 1 octave / min
20 cycles in 3 orthogonal axes
half-sine shaped
Acceleration 15 g, Duration 11 ms,
3 shocks in each direction of 3 orthogonal axes
-5°C to +55°C (+23° F to +131°F)
-5°C to +45°C (+23° F to +112°F)
-20°C to +70°C (-4° F to +158°F)
-25°C to +55°C (-13° F to +131°F)
-25°C to +70°C (-13° F to +158°F)
15% to 95%, condensation not permissible
Active Mini-Starcoupler
14.01.2002

Advertisement

Table of Contents
loading

Table of Contents