Power Supply (LifeSafety FPO75) for Controller (no transformer needed / for US or International):
The LifeSafety FPO75 (75 Watt) Power Supply does not use a plug-in transformer. LifeSafety Power Supply is
compatible for international installations.
CAUTION: Power Input Jumper (JP1) is set 120 VAC/ 60 HZ (Factory Default; i.e. JP1 is closed/not cut).
You must correctly configure the power input JP1 jumper wire – see FlexPower install manual that is shipped
with the power supply. Failure to correctly configure JP1 will cause equipment damage or hazard.
For 120 VAC / 60 Hz input power = JP1 CLOSED (Factory Default) Do not cut JP1 Jumper Wire.
For 230 VAC / 50 Hz input power = JP1 OPEN  Cut the JP1 Jumper Wire (at red dot).
Only use 12VDC Output switch position SW1. Galaxy Controllers do not support 24VDC.
1)
JP1 - AC Input Voltage Jumper (120/230VAC):
 For 120VAC = JP1 is UNCUT (Factory Default)
 For 230 VAC = JP1 Wire must be CUT
2)
J9 - AC Input Connector (3-prong)
3)
LED - AC Power LED (ON/OFF)
4)
JP2 - Earth-Ground Jumper (enable/disable) =
5)
JP3 - Battery Jumper (enable/disable) =
6)
J2/J3 - Battery Connections for back up battery (+/-)
7)
TB1 - Terminal Block for DC Voltage Output Lugs (DC1)
8)
LED - DC Power LED (
ON/OFF
9)
J1
- DC Output Voltage Jumper
(or SW1)
Also:  SYSTEM FLT LED - Can indicate a missing battery when JP3 is "enabled" and AC power is applied/on.
635/600-SERIES H ARDW ARE I NSTALL GUIDE
DISABLED (position 2)
ENABLED (position 1)
)
= must be set to the 12V position!
Chapter-Page 1-5