Troubleshooting

7 Troubleshooting
LED No. Indication
1
Green LED twinkling
2
Green LED blinking
3
No LED active
4
Red LED blinking
5
Red LED blinking
6
Red LED blinking
7
Red LED active
8
Red LED active
Table 7.1 Troubleshooting
®
VLT
ISD Power Supply Module Operating Instructions
Fault
Possible Cause
No output voltage
Signal input "Enable"
not active
Reduced output voltage Signal input "300V" not
active
No output voltage
No AC input voltage
Phases missing
Output voltage possibly
Output current too high Check if output current
reduced
Output voltage possibly
Fan blocked
reduced
Fan speed reduced
Output voltage possibly
Internal heatsink
reduced
temperature too high
No output voltage
Internal heatsink
temperature too high
No output voltage
Internal failure
®
MG75H102 - VLT
is a registered Danfoss trademark
Measures
Comments
Apply 10-28 V to signal
Also possible: connect
input "Enable"
12 V auxiliary voltage
directly at the signal
connector (X3).
Apply 10-28 V to signal
Also possible: connect
input "300 V", if full
12 V auxiliary voltage
output voltage
directly at the signal
(Setpoint U
) is
connector (X3).
o nominal
desired
Check AC input voltage If the power supply
module's external fuse
is blown, there is a
failure in the power
supply module. Send
the power supply
module to Danfoss.
is higher than current I
o
limitation
Check if fan is
If the fan is blocked, the
mechanically locked,
output current is
e.g. by parts
automatically limited to
reaching inside the
4 A.
power supply (fan)
Send the power
supply module to
Danfoss for the fan
to be replaced
Check if air inlet and
If the temperature is
outlet are free
above "Warning Level",
the output current is
Check if the ambient
limited to 4 A.
temperature is too
high
Check if air inlet and
If temperature is above
outlet are free
"Fault Level", the output
is switched off
Check if the ambient
temperature is ≤ the
rated ambient
temperature of the
specification
Contact Danfoss-Service If the external fuse is
broken, do not try to
return the mains
voltage to the power
supply module.