Table 4.1 Liebert Battery Cabinet Specifications (continued)
Battery Cabinet Parameters
Operating Temperature Range
Maximum Altitude Above MSL
1.
Width dimensions are with side panels attached. Subtract 1.4 in. (35 mm) for dimensions without side panels.
2.
Depth dimensions include the front door and rear panel.
3.
Contact the factory about storage at temperatures outside this range.
30
Top-Terminal Cabinet
Relative Humidity
1% Maximum kW derate / 330ft. (100m) rise between 4920-9900 ft. (1500-3000m)
Values
Front-Terminal Cabinet
32°F to 104°F (0 to 40°C)
74°F to 80°F (23-27°C) for optimal battery life
Up to 95% Non-Condensing
(Operating and Non-Operating)
4920ft. (1500m) (as per IEC 62040/3) -