4 SPECIFICATIONS
Table 4.1 Liebert Battery Cabinet Specifications
Battery Cabinet Parameters
Nominal Battery Bus, VDC
Battery Float Voltage, VDC
Minimum EOD Voltage, VDC
Physical Parameters and Standards
Front Door Opening (for serviceability)
Degree of Protection for UPS Enclosure
Minimum Clearance, Top
Minimum Clearance, Back
Minimum Clearance, Sides
Standards and Conformities
Environmental Parameters
Storage Temperature Range
4 Specifications
Battery Type
Standard Width: 56.5 (1435)
1
Width, in. (mm)
Reduced Width: 48.3 (1227)
2
Depth, in. (mm)
Height, in. (mm)
Weight, lb (kg) approx.
Standard Color
Cable Entrance
Values
Top-Terminal Cabinet
VRLA (Valve Regulated Lead-Acid)
480V
540V
384V (for VRLA / Flooded Lead-Acid)
33.5 (850)
76.8 (1950)
See Table 4.4 on page 32
Black (ZP-7021)
More than 180°
IP 20 (with and without front door open)
24" (610mm)
0 in.
0 in.
Top or Bottom
UL 1778; CSA 22.2 107.3
FCC Part 15, Class A; ISTA Procedure 1H; WEEE;
IBC 2012/CBC 2010
-4°F to 104°F (-20°C to 40°C)
74°F to 80°F (23-27°C) for optimal battery life
Front-Terminal Cabinet
63.0 (1600)
33.5 (850)
76.8 (1950)
3
29