Siemens SINAMICS G130 Operating Instructions Manual page 15

Dv/dt filter compact plus voltage peak limiter
Hide thumbs Also See for SINAMICS G130:

Advertisement

NOTICE
Damage to the dv/dt filter compact during continuous operation with low output frequencies
Uninterrupted duty at an output frequency less than 10 Hz can produce thermal overload
and destroy the dv/dt filter.
• Do not operate the drive when using a dv/dt filter compact plus Voltage Peak Limiter
• You may operate the drive for a maximum load duration of five minutes at an output
NOTICE
Damage to the dv/dt filter compact by exceeding the maximum pulse frequency
The maximum permissible pulse frequency when using a dv/dt filter compact is 2.5 kHz or
4 kHz. The dv/dt filter compact can be damaged if the pulse frequency is exceeded.
• When using the dv/dt filter compact, operate the Power Module with a maximum pulse
NOTICE
Damage to the dv/dt filter compact if it is not activated during commissioning
The dv/dt filter compact may be damaged if it is not activated during commissioning.
• Activate the dv/dt filter compact during commissioning via parameter p0230 = 2.
NOTICE
Damage to the dv/dt filter compact if a motor is not connected
dv/dt filters compact which are operated without a motor being connected can be damaged
or destroyed.
• Never operate a dv/dt filter compact connected to the Power Module without a
Note
Cable lengths
Keep the connecting cables to the Power Module as short as possible (max. 5 m). Use an
equivalent cable type when replacing the cables supplied.
dV/dt filter compact plus Voltage Peak Limiter
Operating Instructions, 04/2014, A5E02590131A
continuously with an output frequency less than 10 Hz.
frequency less than 10 Hz, provided that you then select an operation with an output
frequency higher than 10 Hz for a period of five minutes.
frequency of 2.5 kHz or 4 kHz.
connected motor.