Dv/dt filter compact plus voltage peak limiter
Hide thumbs Also See for SINAMICS G130:

Advertisement

Electrical installation
Cable cross-sections
In a dv/dt filter with separate Voltage Peak Limiter (Type 4), the connections between dv/dt
reactor and Voltage Peak Limiter are already installed on the Voltage Peak Limiter.
Table 4- 1
Table 4- 2
Cable type: 600 V, UL style 3271, operating temperature 125° C
Risk of fire due to ground fault/short-circuit
Inadequate installation of the cables to the Power Module DC link can result in a ground
fault/short-circuit and place persons at risk as a result of the associated smoke and fire.
• Comply with local installation regulations that enable this fault to be ruled out.
• Protect the cables from mechanical damage.
• In addition, apply one of the following measures:
Damage to the dv/dt filter compact due to mechanical load on connections
The connections on the dv/dt filter compact have not been designed for the direct
mechanical connection of the motor cables.
• Take line-side measures to ensure that the connections cannot be deformed by the
32
Cable cross-sections for connections between a dv/dt filter and Power Module
dv/dt filter compact plus Voltage Peak Limiter
Connection cable enclosed for connecting dv/dt reactor and Voltage Peak Limiter
Voltage Peak Limiter
Type 4
WARNING
– Use cables with double insulation.
– Maintain adequate clearance, e.g. by using spacers.
– Lay the cables in separate cable ducts or conduits.
WARNING
mechanical load exerted by the connected cables.
Type 1
Type 2
Type 3
Type 4
Cross-section
[mm²]
70
Cross-section
[mm²]
Lug for connecting 1U2 / 1V2 / 1W2 on the
dv/dt reactor
M12
dV/dt filter compact plus Voltage Peak Limiter
Operating Instructions, 04/2014, A5E02590131A
16
25
50
95