CD Automation Revo Revex 2PH Series User Manual page 35

Hide thumbs Also See for Revo Revex 2PH Series:
Table of Contents

Advertisement

REVEX
2PH from 60A to 90A
Parameter Name
Alarm
Function
Option
None
Heater Break
Short Circuit
HB / SC
These option may be
set via communication
only
DEFAULT: Heater Break
Parameter Name
Choose wich parameter is displayed on the home
Startup Display
page at power-up
Description
Choose for which conditions the digital output
indicates alarm. The output always indicate an
alarm when the heat sink is over temperature. The
digital output is energized for normal operating
condition and de-energized when the power
controller is off or when there is an alarm.
Note!: The power controller monitors for heater
break or short circuit condition only when included
in the option selected for Alarm Output Function
SCR is over temperature only
Heater Break or SCR is over temperature
Short circuit or SCR is over temperature
Heater Break or Short circuit
Communication watchdog error
Communication watchdog error or Heater Break
Communication watchdog error or Short circuit
Communication watchdog error, Heater Break or Short circuit
Description
Option
Current
Voltage
Power
DEFAULT: Voltage
Description
Value
0
1
2
1
35
User's manual
Modbus
Default
Address
1
34
Modbus
Default
Address
1
60
Par.
Type
Read
Write
Value
0
1
2
3
16
17
18
19
1
Par.
Type
Read
Write