Electrical Installation
4.4 Cage Clamp Connection Diagram
Figure 4.3 shows the OneGearDrive V210 with terminal box in Y-connection and the connection to the thermal protection.
4
4
Figure 4.3 Cage Clamp Connection Diagram
Description
Motor winding
Protective ground
Temperature protection
KTY 84-130
Table 4.1 Cage Clamp Connections
1) When connected to VLT
information about parameter setting and programming, refer to the corresponding instruction manual.
T1
T2
Table 4.2 Connections T1 and T2
1) Only if connected
NOTICE!
After connection, tighten all four screws on the terminal box cover. The tightening torque is 3 Nm.
14
V1
Inverter output
U
V
W
PE
1)
T1
T2
®
AutomationDrive FC 302 and VLT
®
VLT
AutomationDrive FC 302
KTY 84-130
Danfoss A/S © 08/2015 All rights reserved.
®
VLT
OneGearDrive
W1
U1
U
V
W
PE
U
V
W
Color
Typical cross-section
Black
1.5 mm
Blue
Brown
Yellow/green
1.5 mm
White
0.75 mm
Brown
®
Decentral Drive FCD 302, use analog input terminal 54, KTY sensor 1. For
1)
KTY sensor 1
Analog input 54
T1
T2
Maximum cross-section
2
2
/AWG 16
2.5 mm
/AWG 14
2
/AWG 16
2.5 mm
2
/AWG 14
2
2
/AWG 20
1.5 mm
/AWG 16
®
VLT
Decentral Drive FCD 302
1)
MG75C522
Need help?
Do you have a question about the VLT OneGearDrive and is the answer not in the manual?
Questions and answers