Parameter; Overview Of Module Parameters - Festo cpx-fb13 Manual

Terminal cpx, electrical interface, ctel master module, i-port
Hide thumbs Also See for festo cpx-fb13:
Table of Contents

Advertisement

4
Commissioning
4.6

Parameter

The CTEL master module can be adapted to the respective use situation through the configuration of
various parameters.
In addition, read-only parameters are available for reading out system statuses.
4.6.1

Overview of module parameters

The following table includes an overview of the user-relevant module parameters. The standard set­
tings are shown in bold characters.
Relative
R/
Bit
Address
W
7
Mod. par.
0
RW
6
RW
X
7
RW
Festo – P.BE-CPX-CTEL-EN – 1411a – English
Bit
Bit
Bit
Bit
6
5
4
3
X
X
S
2
.
1
Bit
Bit
Bit
Module parameter
2
1
0
Monitoring U
X
Error control per I-port:
X
I-port 1 configuration
X
I-port 2 configuration
I-port 3 configuration
I-port 4 configuration
Behaviour after I-port short circuit.
CTEL I/O mode
S
S
1
1
.
.
1
2
CTEL I/O length
S
2
.
2
/U
OUT
VAL
0=inactive
1=active
00=Use existing device
01=Expect device
10=Port inactive
0=Leave switched off
1=Switch on again
1)
00=Automatic config.
01=Only outputs (fixed length)
10=Only inputs (fixed length)
11=I/O (fixed length)
1)
00=2 bytes per I-port
01=4 bytes per I-port
10=6 bytes per I-port
11=8 bytes per I-port
35

Advertisement

Table of Contents
loading

Table of Contents