Description
Electronics
8034116
1405NH
[8034124]

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CPX-CTEL-2-M12-5POL-LK and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Festo CPX-CTEL-2-M12-5POL-LK

  • Page 1 Terminal CPX Electrical interface CPX-CTEL-2-M12-5POL-LK Description Electronics 8034116 1405NH [8034124]...
  • Page 2 Essential or useful accessories. Information on environmentally sound usage. Text designations: • Activities that may be carried out in any order. 1. Activities that should be carried out in the order stated. – General lists. Festo – P.BE-CPX-CTEL-LK-EN – 1405NH –...
  • Page 3: Table Of Contents

    Electrical interface CPX-CTEL-2-M12-5POL-LK Table of contents – Electrical interface CPX-CTEL-2-M12-5POL-LK Safety and requirements for product use ........
  • Page 4 ..... . Commissioning with the Festo Maintenance Tool software (CPX-FMT) ....
  • Page 5 – Revision R2 Note • With newer firmware versions, check whether there is a newer version of this description available ( www.festo.com). Service Please consult your regional Festo contact if you have any technical problems. Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 6: Safety And Requirements For Product Use

    The module is intended exclusively for use in CPX terminals from Festo for installation in machines or automated systems and may be used only in the following ways: –...
  • Page 7 CPX system description (P.BE-CPX-SYS-...). Note In the event of damage caused by unauthorised manipulation or other than intended use, the warranty is invalidated and the manufacturer is not liable for damages. Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 8: Requirements For Product Use

    A.1 Technical data). The product-relevant EC directives can be found in the declaration of conformity. Certificates and the declaration of conformity for this product are found on the Internet page of Festo ( www.festo.com). Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 9: Overview

    Overview Overview Product overview Festo can assist you in solving your automation task at the machine level with the aid of valve terminals and I/O modules. The electrical interface CPX-CTEL-2-M12-5POL-LK permits connection of devices with IO-Link interface (devices) to a CPX system.
  • Page 10: Io-Link

    The IO-Link network system serves to exchange serial data from decentralised function modules (devices) at the field level. The electrical interface CPX-CTEL-2-M12-5POL-LK has 2 interfaces (ports) that, with few limitations, support connection of IO-Link devices. The limitations compared to the IO-Link standard are: –...
  • Page 11: Pin Allocation

    The LED indicators X3 and X4 are without function, since the corresponding ports are not used. 2.3.1 Overview of LED indicators X1 (status port X1) Module fault X2 (status port X2) PL (load voltage supply) X3 (without function) PS (power supply) X4 (without function) Fig. 2.3 Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 12: Behaviour And Significance Of The Led Indicators

    “OK” (LED illuminated green). The port at which the error occurred can be determined through the FMT or MMI of the diagnostic messages. Information on error elimination 5.2.2 Diagnostic/error messages by CPX error numbers). Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 13: Addresses

    Setting is made via DIL switches on the left side of the module, directly below the housing cover Fig. 2.4). These are only accessible if the module is removed from the interlinking block 3.2 Mounting/dismounting). Fig. 2.4 Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 14 This setting is applicable for both ports in common (maximal 16 bytes per port). The DIL switch group 2 has no function with this product. DIL switch 1 S1.1 S1.2 Function 4 bytes I/O 8 bytes I/O 12 bytes I/O 16 bytes I/O Tab. 2.4 Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 15: Mounting And Installation

    They will help you avoid damage to the electronics. Note • Handle all modules and components carefully. • Comply with the specified torques. Information about mounting of the CPX terminal can be found in the CPX system descrip- tion (P.BE-CPX-SYS-...). Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 16: Mounting/Dismounting

    DIL switches, since they can no longer be reached after mounting 2.4.2 Setting of the I/O configuration presetting). Module Contact rails Interlinking block Screws 1) Here with additional power supply as an example Fig. 3.1 Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 17: Connecting Cables

    Connecting cables Note Malfunction due to impermissible cabling. • If possible, use only specified connecting cables from Festo to connect the devices to the module ( www.festo.com/catalogue). • Observe the maximum length of 20 m for the connecting cables used to connect the devices.
  • Page 18: Connection Of Devices

    3. With the inscription labels (type IBS 6x10 or IBS 9x20), mark the port to which the device is connec- ted. In this way you can avoid confusion during later repair and maintenance work. Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 19: Connecting The Power Supply

    • The total current requirement of the CPX terminal and the connected devices as well as the limit values for the maximum current intensities must be taken into account in the design of the power supply ( 3.5.2 Determining the current consumption). Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 20: Determining The Current Consumption

    Sum of current consumption (module + devices) =______ A 1) See manufacturer’s specifications Tab. 3.1 An additional power supply of 1.6 A per port can be made available through the load voltage supply U Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 21: Connection With The Host System

    • Seal unused ports with corresponding protective caps from our catalogue (not in- cluded in delivery, www.festo.com/catalogue). The ports X3 and X4 are without function and sealed at the factory with a protective cap. Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 22: Commissioning

    Only after the CPX terminal is completely run up and a connection is made to the host system is activation by parameter of the load voltage supply (PL) possible 4.6.4 Parameter “port settings”). Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 23: Address Assignment In The Cpx System

    Byte 0 Byte 1 Byte 1 Port 2 (8 bytes) Byte 2 Byte 2 … … Byte 7 Byte 7 Legend: White = assigned; grey = unused Unused bytes are filled with 0. Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 24: Procedure For Commissioning

    • Check whether the current consumption of the connected devices and the other CPX modules cor- responds to the specifications and limit values ( 3.5 Connecting the power supply). • Check the power supply connections at the interlinking blocks. Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 25: Behaviour In Case Of Malfunctions In Operation

    The behaviour of the affected device is dependent on the device type. Moreover, additional diagnostic information of the module is available and can be called up both via the fieldbus used as well as via the Festo Maintenance Tool software (CPX-FMT) or the operator unit (CPX- MMI).
  • Page 26: Parameters

    8 bytes (hexadecimal) Data 8 … 15 31 … 38 8 bytes (hexadecimal) Data 16 … 23 39 … 46 8 bytes (hexadecimal) Data 24 … 31 Mailbox-CTRL Port START BUSY READY ERROR Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 27: Parameter "Behaviour After Port Short Circuit

    – remain switched off (setting “Leave switched-off ”) or – automatically be switched back on (setting “Switch back on”). With access via the Festo Maintenance Tool software (CPX-FMT) or the operator unit (CPX-MMI), the parameter can be selected and changed separately.
  • Page 28: Commissioning With The Operator Unit (Cpx-Mmi)

    • Port 1 - PL supply • Port 2 - PL supply … “Monitoring/forcing” menu (also “Fail safe”) ( 4.7.2 Observe signal statuses (monitoring)) “Parameters” menu ( 4.7.3 Parameterisation with the operator unit (CPX-MMI)) Fig. 4.1 Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 29: Observe Signal Statuses (Monitoring)

    Fig. 4.3). System overview Monitoring/forcing (M) Diagnostics (D) 2:CTEL-2-LK :P Parameters (P) Monitor V : … Fail safe (F) Behaviour after port… Module data (MD) IO-Link port setup: … Parameter module Fig. 4.3 Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 30: Commissioning With The Festo Maintenance Tool Software (Cpx-Fmt)

    Commissioning Commissioning with the Festo Maintenance Tool software (CPX-FMT) The Festo Maintenance Tool software (CPX-FMT) can also be used for commissioning, parameterisation and extended diagnostics of the module. You can find the current software version in the Internet www.festo.com/sp). The module parameters are depicted in the following diagram as an example ( Fig.
  • Page 31: Diagnostics And Error Handling

    (CPX-FMT) soft- diagnostics also possible from a higher ware automation level. Tab. 5.1 Note The available diagnostic information may depend on the settings of the CPX bus node or on the parameterisation. Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 32: Diagnostics/Error Messages

    – Within a CPX terminal, diagnostic/error messages of inputs have priority over dia- gnostic/error messages of outputs. This principle of error prioritisation is also used in the module described here. Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 33: Diagnostic/Error Messages By Cpx Error Numbers

    – device temperature limit exceeded • Check installation – primary voltage/main power supply too • Check power supply Process variable range underflow • Process data inconsistent, check Process variable range overflow • Process data inconsistent, check Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 34: Diagnostics Via Led Indicators

    LED indicators for diagnostics of the CPX terminal are available on the module and the devices. Descrip- tion of the LED indicators on the module ( 2.3 LED indicators). Significance of the LED indicators on the devices can be found in the description of the respective module. Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 35: Diagnostics Via The Cpx Bus Node

    CPX terminal. The devices connected to a module are treated as input or output addresses within the CPX terminal. Detailed information on the I/O diagnostic interface and diagnostic memory can be found in the CPX system description (P.BE-CPX-SYS-…). Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 36: Diagnostics With The Operator Unit (Cpx-Mmi)

    Module data (MD) … “Diagnostics” menu Fig. 5.1 General information on the operation and commissioning of the CPX terminal using the operator unit can be found in the description for the operator unit (P.BE-CPX-MMI-1-…). Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 37: Diagnostics With The Festo Maintenance Tool (Cpx-Fmt)

    Diagnostics and error handling Diagnostics with the Festo Maintenance Tool (CPX-FMT) The Festo Maintenance Tool (CPX-FMT) software offers extended functions for diagnostics and troubleshooting. Fig. 5.2 General information on operating and commissioning the CPX terminal with the CPX-FMT software can be found in the CPX system description (P.BE-CPX-SYS-…) and in the online help of the CPX-FMT software.
  • Page 38: Behaviour After Lost Connection To The Device

    I/O configuration 8 bytes Device: 4 bytes Port Byte 0 Byte 0 Byte 1 Byte 1 Byte 2 Byte 2 Byte 3 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Tab. 5.5 Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 39: Behaviour In The Event Of Power Supply Errors

    (PS) and load voltage supply (PL). Behaviour after elimination of the error can be set via the parameter “Behaviour after port short cir- cuit” ( 4.6.3 Parameter “Behaviour after port short circuit”). Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 40: A Technical Appendix

    Wall and H-rail mounting: SG 1 1) Note that connected devices might only fulfil a lower degree of protection. 2) Cover caps from Festo, type ISK-M12, for ports X3 and X4, included in delivery. Tab. A.1 Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 41 ) and load voltage supply, EL/SEN valves (U – supply PS/PL between the ports Functional earth connection Optional, through earthing plate Mains buffering time 10 ms corresp. IEC 1131, part 2 Tab. A.2 Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 42 Communication errors Communication errors Short-circuit PS/PL Device error Trigger level, undervoltage identification PS Approx. 17.5 V (measured in the module) Hysteresis undervoltage identification PS Approx. 500 mV (measured in the module) Tab. A.3 Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 43: Event Codes

    0x7711 Device Mass error – check installation 0x8C00 Device Technology-specific application error – device reset 0x8C10 Device Process variable range overflow – process data inconsistent 0x8C20 Device Measuring range exceeded – check application Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 44: Accessories

    Process variable range underflow – process data inconsistent 0x8C40 Device Maintenance required – cleaning 0x8C41 Device Maintenance required – refill 0x8C42 Device Maintenance required – replace wearing parts Tab. A.4 Accessories Accessories www.festo.com/catalogue Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 45: B Glossary

    Provide the connection to specific fieldbuses. Communicate with connected I/O modules and monitor their functionality. CPX-FMT Festo Maintenance Tool. PC software for commissioning, configuration and extended diagnostics of CPX terminals. CPX-MMI Multi-media interface, operator unit for reading and configuring CPX systems.
  • Page 46 ......Commissioning – with the Festo Maintenance Tool software Festo Maintenance Tool ....
  • Page 47 ....... – “Monitoring U ” ....Festo – P.BE-CPX-CTEL-LK-EN – 1405NH – English...
  • Page 48 Copyright: Festo AG & Co. KG Postfach 73726 Esslingen Germany Phone: +49 711 347-0 Fax: +49 711 347-2144 e-mail: service_international@festo.com Reproduction, distribution or sale of this document or communica- tion of its contents to others without express authorization is Internet: prohibited.