Control cabinet design
8.4 Connection system
Example of MOTION-CONNECT 500 (segment length 10 m, 1 DQE, 1 HCB):
100 m - 10 m - 5 m • 2 = <100 m
8.4.8

Connectable conductor cross-sections for screw terminals

The type of screw terminal can be taken from the interface description of the particular
component.
Table 8-8
Screw terminals
Screw terminal type
1 (X21 AM600)
5 (X24)
(24 V terminal adapter)
8.4.9

Routing cables in a damp environment

NOTICE
Damage to the S120M due to incorrect cable routing in a humid environment
Incorrect cable routing can allow moisture to enter the housing of the S120M, which can lead
to failures and damage.
● In a humid environment, route the power and signal cables only as shown in the diagram
146
Connectable conductor
cross-sections
Stripping length
Tool
Tightening torque
Connectable conductor
cross-sections
Stripping length
Tool
Tightening torque
below on the left.
Rigid, flexible
with end sleeve, without plastic sleeve
with end sleeve, with plastic sleeve
AWG/kcmil
7 mm
Screwdriver 0.4 x 2.0 mm
0.22 to 0.25 Nm (1.9 ... 2.2 lbf in)
Flexible
with end sleeve, without plastic sleeve
with end sleeve, with plastic sleeve
AWG/kcmil
12 mm
Screwdriver 1.0 x 4.0 mm
1.2 to 1.5 Nm (10.6 ... 13.3 lbf in)
0.08 mm
to 1.5 mm
2
0.25 mm
to 1.5 mm
2
0.25 mm
to 0.5 mm
2
28 ... 14
0.5 mm
to 6 mm
2
0.5 mm
to 6 mm
2
0.5 mm
to 6 mm
2
20 ... 8
Manual, 06/2019, 6SL3097-5AW00-0BP1
2
2
2
2
2
2